| Plan Review Notes For Permit 08070794 |
| Permit Number |
08070794 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-30 13:44:17 | RESIDENTIAL (R3) WINDOWS AND SHUTTERS BUILDING REVIEW | | | CHECKLIST. | | | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. | | | | | | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY | | | SEC. 713.13 FLORIDA STATUTE. | | | | | | 2-SINGLE HUNG NOA 07-0521.06 EXPIRED ON JULY 11, | | | 2008. NEED TO PROVIDE CURRENT PRODUCT APPROVAL(2 | | | COPIES) AS REQUIRED BY DCA RULE 9B-72. | | | | | | 3- CLARIFY SHUTTER SPAN SIZE SHOWN ON COLUMN 6 OF | | | INSTALLATION SCHEDULE SUBMITTED.EG: OPENING #1 IS | | | 72" WIDE AND SHUTTERS ARE INSTALLED HORIZONTALLY. | | | WHAT'S THE EDGE DISTANCE BEING CONSIDERED IF THE PANEL | | | IS 84" LONG? . THIS APPLIES TO ALL OPENINGS.ANCHORS | | | ARE TO BE ATTACHED DIRECTLY TO THE WOOD FRAMING, NOT TO | | | THE PLYWOOD SHEATHING. | | | | | | 4- ANCHOR SPACING SHOWN ON THE INSTALLATION SCHEDULE | | | CAN'T BE 13". SEESHUTTER CROSS SECTION ON SHEET 1 OF | | | 5. SHUTTER MOUNTING HOLES ARE SPACED AT 12 1/2" O.C.. | | | REVISE AS REQUIRED. | | | | | | 5- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION | | | IS TOO LOW. SEC. 108.3 CITY AMENDMENTS TO FBC 2004.A | | | VALUE OF $3,700 IS TOO LOW FOR REPLACEMENT OF 26 | | | WINDOWS, 9 MULLIONS AND INSTALLATION OF STORM SHUTTERS | | | ON EACH OPENING. UPDATE VALUATION AS REQUIRED TO | | | REFLECT COMPLETE SCOPE OF WORK. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|