Plan Review Notes
Plan Review Notes For Permit 08070794
Permit Number 08070794
Review Stop B
Sequence Number 1
Notes
Date Text
2008-07-30 13:44:17RESIDENTIAL (R3) WINDOWS AND SHUTTERS BUILDING REVIEW
 CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 2-SINGLE HUNG NOA 07-0521.06 EXPIRED ON JULY 11,
 2008. NEED TO PROVIDE CURRENT PRODUCT APPROVAL(2
 COPIES) AS REQUIRED BY DCA RULE 9B-72.
  
 3- CLARIFY SHUTTER SPAN SIZE SHOWN ON COLUMN 6 OF
 INSTALLATION SCHEDULE SUBMITTED.EG: OPENING #1 IS
 72" WIDE AND SHUTTERS ARE INSTALLED HORIZONTALLY.
 WHAT'S THE EDGE DISTANCE BEING CONSIDERED IF THE PANEL
 IS 84" LONG? . THIS APPLIES TO ALL OPENINGS.ANCHORS
 ARE TO BE ATTACHED DIRECTLY TO THE WOOD FRAMING, NOT TO
 THE PLYWOOD SHEATHING.
  
 4- ANCHOR SPACING SHOWN ON THE INSTALLATION SCHEDULE
 CAN'T BE 13". SEESHUTTER CROSS SECTION ON SHEET 1 OF
 5. SHUTTER MOUNTING HOLES ARE SPACED AT 12 1/2" O.C..
 REVISE AS REQUIRED.
  
 5- PERMIT VALUATION DECLARED IN THE PERMIT APPLICATION
 IS TOO LOW. SEC. 108.3 CITY AMENDMENTS TO FBC 2004.A
 VALUE OF $3,700 IS TOO LOW FOR REPLACEMENT OF 26
 WINDOWS, 9 MULLIONS AND INSTALLATION OF STORM SHUTTERS
 ON EACH OPENING. UPDATE VALUATION AS REQUIRED TO
 REFLECT COMPLETE SCOPE OF WORK.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712