| 2008-08-11 15:39:17 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEWSECOND |
| | CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- INSTALLATION SCHEDULE SUBMITTED SHOWS EDGE DISTANCE |
| | TO BE 3". NEED TO REVISE ANCHOR SPACING AS REQUIRED BY |
| | EDGE DISTANCE VERSUS SPACING FOR ANCHORS ON SHEET7 OF |
| | 10OF DRAWING 07-085 SUBMITTED (NEW PRODUCT APPROVAL |
| | SUBMITTED THIS TIME).ANCHOR SPACING IS BASED ON EDGE |
| | DISTANCE OF 3 1/2". OTHERWISE NEED TO REDUCE THE ANCHOR |
| | SPACINGBY MULTIPLYINGBY 0.83 SINCE EDGE DISTANCE |
| | SHOWN ON INSTALLATION SCHEDULE IS 3". (REPEAT |
| | COMMENT). |
| | |
| | 2-CLARIFY SHUTTER SPAN SHOWN ON COLUMN 6 OF |
| | INSTALLATION SCHEDULE.EG: IFOPENING #1 IS 64" HIGH |
| | HOW COME SHUTTER SPAN IS ONLY 68"IF THE EDGE DISTANCE |
| | ON COLUMN 8 IS 3".SEE SHEET 4 OF 10 OF DRAWING |
| | 07-085 TO SEE HOW IS THE PANEL SPAN DIMENSIONED.THIS |
| | COMMENT APPLIES TO ALL OPENINGS.PANEL SPAN DOESN'T |
| | REFLECT SIZE OF OPENING AND EDGE DISTANCE.ALSO, |
| | REMEMBER THAT EDGE DISTANCE EXCLUDES STUCCO FINISH OR |
| | ANY OTHER WALL FINISH. REVISE AS REQUIRED. (REPEAT |
| | COMMENT). |
| | |
| | 3- REVISE TAPCON SIZE TO REFLECT MINIMUM EMBEDMENT |
| | REQUIRED FOR CONCRETE AND CONCRETE BLOCKSUBSTRATE. |
| | SEE SHEET 7 OF 10FOR MINIMUM EMBEDMENT REQUIRED AND |
| | REVISE AS REQUIRED. (REPEAT COMMENT). |
| | NOTE:MINIMUM EMBEDMENT DOESN'T INCLUDE STUCCO |
| | THICKNESS. |
| | |
| | 4- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT). |
| | |
| | 5- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC. |
| | 108.3 CITY AMENDMENTS TO FBC 2004.THEREFORE, OWES |
| | $32.81 FOR UPDATED VALUATION. (REPEAT COMMENT. FEES NOT |
| | PAID YET). |
| | |
| | 6- NEW PRODUCT APPROVAL WAS SUBMITTED.THE MAXIMUM |
| | PANEL SPAN IS 7'-6".SEE SHEET 8 OF 10 OF DRAWING |
| | 07-085.ACCORDING TO THIS LIMITATION PRODUCT APPROVAL |
| | IS NOT GOOD FOR OPENINGS 4 THRU 8.NEED TO PROVIDE |
| | ANOTHER PRODUCT APPROVAL. |
| | |