| 2008-07-29 16:57:25 | RESIDENTIAL (R3) SHUTTERS, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- INSTALLATION SCHEDULE SUBMITTED SHOWS EDGE DISTANCE |
| | TO BE 3". NEED TO REVISE ANCHOR SPACING AS REQUIRED BY |
| | EDGE DISTANCE VERSUS SPACING FOR ANCHORS ON SHEET14 |
| | OF 28.ANCHOR SPACING IS BASED ON EDGE DISTANCE OF 3 |
| | 1/2". OTHERWISE NEED TO REDUCE THE ANCHOR SPACINGBY |
| | MULTIPLYING0.83 SINCE EDGE DISTANCE SHOWN ON |
| | INSTALLATION SCHEDULE IS 3". |
| | |
| | 2-PRODUCT APPROVAL SUBMITTED FL7288-R1WITH DRAWING |
| | 06-174 WAS REVISED BY FL7288-R2 WITH DRAWING 07-184. |
| | NEED TO PROVIDE CURRENT FLORIDA PRODUCT APPROVAL |
| | FL7288-R2 AND CORRESPONDING DRAWING 07-184. |
| | |
| | 3- CLARIFY SHUTTER SPAN SHOWN ON COLUMN 5 OF |
| | INSTALLATION SCHEDULE.EG: IFOPENING #1 IS 64" HIGH |
| | HOW COME SHUTTER SPAN IS ONLY 43".THIS COMMENT |
| | APPLIES TO ALL OPENINGS.PANEL SPAN DOESN'T REFLECT |
| | SIZE OF OPENING. REVISE AS REQUIRED. |
| | |
| | 4- REVISE ANCHOR SPACING.INSTALLATION SCHEDULE CALLS |
| | FOR2 1/4" TAPCONS, BUT ANCHOR TYPE HIGHLIGHTED ON |
| | SHEET13 OF 26IS FOR ALL POINTS SOLID-SET ANCHOR. |
| | AND ANCHOR TYPE HIGHLIGHTED ON SHEET 15 OF 26IS FOR |
| | WEDGE-BOLT.REVISE AS REQUIRED TO MATCH ANCHOR SPACING |
| | FOR TAPCONS AS SHOWN ON INSTALLATION SCHEDULE. (NOTE: |
| | KEEP THIS IN CONSIDERATION WHEN USING REVISED DRAWING |
| | 07-184. SEE ITEM #2 ABOVE). |
| | |
| | 5- REVISE TAPCON SIZE TO REFLECT MINIMUM EMBEDMENT |
| | REQUIRED FOR CONCRETE AND CONCRETE BLOCKSUBSTRATE. |
| | SEE SHEET 14 OF 26 FOR MINIMUM EMBEDMENT REQUIRED AND |
| | REVISE AS REQUIRED. |
| | |
| | 6- INFORMATION SHOWN ON THE SUBSTRATE COLUMN OF |
| | INSTALLATION SCHEDULE IS NOT CLEAR.IS IT CONCRETE, |
| | CONCRETE BLOCK OR WOOD? |
| | |
| | 7-PERMIT APPLICATION AND KEY PLAN SHOW 8OPENINGS, |
| | WHILE INSTALLATION SCHEDULE ONLY SHOW 7 OPENINGS. |
| | PROVIDE COMPLETE INFORMATION. |
| | |
| | 8-PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. |
| | |
| | 9- PERMIT VALUATION WAS UPDATED AS REQUIRED BY SEC. |
| | 108.3 CITY AMENDMENTS TO FBC 2004.THEREFORE, OWES |
| | $32.81 FOR UPDATED VALUATION. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |