| 2008-08-29 15:44:45 | |
| | |
| | |
| | |
| | |
| | ** DENIED ** |
| | |
| | |
| | |
| | 1) NOTE: PLANS NEED TO INDICATE THE MINIMUM CODES AS |
| | NOTED BELOW FOR DESIGN. |
| | 2004 FBC W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE 230.2, 230.2E. PLEASE PROVIDE |
| | INFORMATION ON HOW NEW SERVICE CAN BE GRANTED AND ALSO |
| | SEE THE PLANS DO NOT LABEL MAINS. |
| | |
| | 3) NOTE: PLEASE SEE TITLE 47 PART 12.2 OF THE FEDERAL |
| | CODE OF REGULATIONS AND PROVIDE MINIMUM BACK UP TIMES |
| | AND SOURCE FOR SYSTEM EQUIPMENT. |
| | |
| | 4) NOTE: PLEASE SEE CODES REFLECTED IN NOTES ARE NOT |
| | FROM THE 2005 NEC. |
| | |
| | 5) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR FEEDERS PER |
| | 13-413.1ABC.1. |
| | |
| | 6) NOTE: AT THIS TIME THERE IS NOTHING ON PLANS FOR ANY |
| | LIGHTING OR SERVICE RECEPTACLES. PLEASE VERIFY. |
| | LIGHTS IN ROOM? |
| | FBC 106.1.1 |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |