2008-08-29 15:44:45 
  
  
  
  
 ** DENIED **
  
  
  
 1) NOTE: PLANS NEED TO INDICATE THE MINIMUM CODES AS
 NOTED BELOW FOR DESIGN.
 2004 FBC W/ 2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE 230.2, 230.2E. PLEASE PROVIDE
 INFORMATION ON HOW NEW SERVICE CAN BE GRANTED AND ALSO
 SEE THE PLANS DO NOT LABEL MAINS.
  
 3) NOTE: PLEASE SEE TITLE 47 PART 12.2 OF THE FEDERAL
 CODE OF REGULATIONS AND PROVIDE MINIMUM BACK UP TIMES
 AND SOURCE FOR SYSTEM EQUIPMENT.
  
 4) NOTE: PLEASE SEE CODES REFLECTED IN NOTES ARE NOT
 FROM THE 2005 NEC.
  
 5) NOTE: PLEASE PROVIDE VOLTAGE DROP FOR FEEDERS PER
 13-413.1ABC.1.
  
 6) NOTE: AT THIS TIME THERE IS NOTHING ON PLANS FOR ANY
 LIGHTING OR SERVICE RECEPTACLES. PLEASE VERIFY.
 LIGHTS IN ROOM?
 FBC 106.1.1
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  