| 2008-08-05 09:41:24 | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-1 FLOOR PLAN: CLEARLY IDENTIFY ALL PLUMBING |
| | FIXTURES ON THE FLOOR PLAN. PER FBC-20004 PLUMBING |
| | SECTION 401.1 SCOPE. |
| | |
| | 2. SHEET A-4 SANITARY ISOMETRIC RISER DIAGRAM: THE |
| | SUBMITTED ISOMETRIC DOES NOT REFLECT THE FLOOR PLAN ON |
| | SHEET A-1. THE LAVATORIES, TUB, AND SHOWER ARE BEING |
| | INDICATED IN THE WRONG LOCATIONS. PLEASE PROVIDE A FLAT |
| | FLOOR PLAN DRAWING OF THE UNDERGROUND SANITARY PLUMBING |
| | AND CORRELATE THE RESUBMITTED SANITARY PLUMBING |
| | ISOMETRIC ACCORDINGLY. PER FBC-2004 PLUMBING SECTION |
| | 701.1 SCOPE. |
| | |
| | 3. SHEET A-4 SANITARY ISOMETRIC RISER DIAGRAM: |
| | CLEANOUTS ARE REQUIRED AT THE BASE OF THE LAVATORY |
| | WASTE STACKS AND CLEARLY INDICATE THE CLEANOUT AT THE |
| | JUNCTION OF THE BUILDING DRAIN AND BUILDING SEWER AS |
| | BEING A TWO-WAY CLEANOUT. PER FBC-2004 PLUMBING SECTION |
| | 708.3.4 BASE OF STACK AND SECTION 708.3.5 BUILDING |
| | DRAIN AND BUILDING SEWER JUNCTION. |
| | |
| | 4. SHEET A-1 FLOOR PLAN AND A-4 ELECTRICAL PLAN ARE |
| | INDICATING THE FOLLOWING "ADD NEW SHOWER HEAD W/ |
| | CONTROLS". PLEASE CLARIFY IF THIS IS AN OUTSIDE SHOWER. |
| | IF THIS IS AN OUTSIDE SHOWER WHY IS IT NOT BEING |
| | INDICATED ON THE ELEVATION DRAWINGS ON SHEET A-1. IF |
| | THIS IS AN OUTSIDE SHOWER CLEARLY INDICATE WHERE IT IS |
| | GOING TO DRAIN (SUCH AS A GRASSY AREA). PER FBC-2004 |
| | PLUMBING SECTION 417. |
| | |
| | 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | (SHEET A-4 HAS NO ONE TAKING RESPONSIBILITY FOR IT) |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |