| 2008-08-12 16:54:42 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1-PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS FOR WINDOW TO BE REPLACED IN |
| | LIVING ROOM. |
| | B PRECAST LINTELS. |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS AND DETAILS. |
| | |
| | 2- ENGINEER TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | NOTE: MAY USE THE STANDARD SHOP DRAWINGS APPROVAL STAMP |
| | OR ANY OTHERWRITING METHOD. |
| | |
| | 3- PROVIDE NOTICE OF COMMENCEMENT. SEC. 713.13 FLORIDA |
| | STATUTE. |
| | ***NOTE: THIS MAY BE PROVIDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 4- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD |
| | (561)233-5120) TO VERIFY IF IMPACT FEES ARE DUE.BRING |
| | BACK STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE |
| | DUE. |
| | |
| | 5- PROVIDE ENERGY CALCULATIONS. SEC. 13-101.2.2FBC |
| | 2004. PLEASE MAKE SURE CORRECT AND UPDATED FORM IS USED |
| | TO AVOID DELAYS. |
| | |
| | 6-SPECIFY HOWTHE1X6 T & G SHEATHING ON NEW PORCH |
| | (DETAIL A/A-3)IS GOING TO BE FASTENED. ROOF SHEATHING |
| | NAILING SCHEDULE ON SHEET A-3 DOESN'T APPLY TO THIS |
| | TYPE OF SHEATHING. |
| | |
| | 7- TYPICAL WALL SECTION ON SHEET A-2: |
| | A) FOOTING SIZE DOESN'T MATCH SIZE SHOWN ON |
| | FOUNDATION PLAN. REVISE AS REQUIRED. |
| | B) SPECIFY FOOTING EMBEDMENTBELOW GRADE TO VERIFY |
| | COMPLIANCE WITH SEC. R406.1.4 OF 2004 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 8- OWES $3.28 FOR RADON FEES. |
| | |
| | 9- SHEET A-3: |
| | A) WIND INFORMATION: UPDATE NOTE #6.FOR ONE & TWO |
| | FAMILY RESIDENCES THE CODE TO BE REFERENCED IS THE 2004 |
| | FLORIDA RESIDENTIAL CODE (SEE SEC. R301),NOT CHAPTER |
| | 16 OF FBC. REVISE AS REQUIRED. |
| | ALSO, UPDATENOTE BELOWNOTE #15. CURRENTREVISIONS |
| | ARE 2007, NOT 2006. |
| | |
| | B) TYPICAL PORCH SECTION: REVISESECTION CITED FOR |
| | SHINGLES.BUILDING IS REVIEWED UNDER THE 2004 FLORIDA |
| | RESIDENTIAL CODE, NOT THE 2004 FBC. |
| | |
| | 10- SURVEY NEEDS TO HAVE SURVEYOR'S ORIGINAL SIGNATURE, |
| | NOT COPY AS REQUIRED BY SEC. 61G17-7.0025 OF FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER472 FLORIDA STATUTE. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |