| 2008-08-12 15:44:18 | |
| | ** DENIED PLANS.** |
| | |
| | |
| | 1) NOTE: PLEASE SEE BUILDING REVIEW COMMENTS AS PLANS |
| | SPECIFICALLY STATE POLES ARE TO BE RATED FOR *100 |
| | MPH*. |
| | PLEASE KNOW THE MINIMUM DESIGN IN THIS AREA FOR THE |
| | CITY OF WEST PALM BEACH WIND ZONE IS 140MPH 3-SECOND |
| | GUST. |
| | THIS IS NOTED FOR INFORMATION ONLY AND NOT A BUILDING |
| | PLAN REVIEW NOTE. |
| | |
| | 2) NOTE: PLEASE SEE *C* SHEETS WHICH ONLY CONTAIN A |
| | SIGNATURE AND DO NOT CONTAIN ANY RAISED SEAL AS |
| | REQUIRED PER FAC 61G15-23.002, FS 471.025 |
| | |
| | 3) NOTE: PLEASE PROVIDE SITE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2.ABC.1.3 |
| | |
| | 4) NOTE: PLEASE PROVIDE INFORMATION FOR LIGHTING |
| | CONTROLS PER 13-415.1.ABC.1.4. |
| | |
| | 5) NOTE: PLEASE PROVIDE VOLTAGE DROP PER |
| | 13-413.1.ABC.1.1, .1.2 |
| | |
| | 6) NOTE: RECORD PLANS NEED TO INDICATE THE NEW ADDED |
| | LOADS TO EXISTING SERVICE AND EQUIPMENT. |
| | NEC 220 |
| | FBC 106.5, 106.1.1 |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |