| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | REPEAT COMMENTS FROM THE PREVIOUS REVIEW***INDICATES |
| | FURTHER EXPLANATION OF PREVIOUS COMMENT |
| | |
| | 1} THE MANUFACTURERS SPECIFICATION FOR THE GENERATOR |
| | ARE PARTIALLY INDISCERNIBLE, PLEASE SUBMIT READABLE |
| | COPIES***THE SAME SPEC'S RESUBMITTED. |
| | |
| | 2} THE RESPONSE TO THE PREVIOUS REVIEW COMMENT #3WAS |
| | THAT THE OCP IS IN THE GENERATOR CONTROL PANEL, THERE |
| | IS NO INDICATION OF THAT IN THE SPECIFICATIONS |
| | SUBMITTED.***CORRECT, THE 3000AMP OCP IS NOTED ON SHEET |
| | E2. |
| | |
| | 3} INDICATE IF ANY REQUIRED EMERGENCY LIGHTING OR OTHER |
| | SYSTMS WILL OPERATE FROM THIS GENERATOR POWER.PROVIDE A |
| | RISER DIAGRAM INDICATING WHICH PANELS WILL BE FED FROM |
| | THIS GENERATOR. THE SUBMITTED PLAN SHOWS THE GENERATOR |
| | FEEDING "MDP."*** NO RESPONSE GIVEN TO THIS COMMENT. |
| | |
| | NEW COMMENT GENERATED AS THE DISCONNECTING MEANS IN THE |
| | NEXGEAR NOW IS THE FIRST MEANS OF DISCONNECT. |
| | |
| | 4} SHEET E2, NOTE #9 DOES NOT INCLUDE AN EQUIPMENT |
| | GROUNDING CONDUCTOR PER 250.130(A) FOR GROUNDED SYSTEMS |
| | THE CONNECTION SHALL BE MADE BY BONDING THE EQUIPMENT |
| | GROUNDING CONDUCTOR TO THE GROUNDED SERVICE CONDUCTOR |
| | AND THE GROUNDING ELECTRODE CONDUCTOR. THEREFORE AS THE |
| | EQUIPMENT GROUND ORIGINATES FROM THE FIRST MEANS OF |
| | DISCONNECT IT MUST BE RUN WITH THE FEEDERS FROM |
| | "NEXGEAR" SWITCHGEAR. "250.32(2)(B) GROUNDED CONDUCTOR |
| | WHERE (1) AN EQUIPMENT GROUNDING CONDUCTOR IS NOT RUN |
| | WITH THE SUPPLY TO THE BUILDING OR STRUCTURE, (2) THERE |
| | ARE NO CONTINUOUS METALLIC PATHS BONDED TO THE |
| | GROUNDING SYSTEM IN EACH BUILDING OR STRUCTURE |
| | INVOLVED,".THE CONTINUOUS PATH IS THE CONTROL |
| | WIRING.SEE SHEET E6 AND E4.***THE NEXGEAR IS THE FIRST |
| | MEANS OF DISCONNECT SEE 250.24(A)(5). NOT ALL CONTROL |
| | WIRING WILL GO TO NORMALLY OPEN CONTACTS. SEE NOTES ON |
| | SHEET *6. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |