| 2008-09-29 13:33:49 | PLUMBING PLAN REVIEW: |
| | DENIED **2ND TIME: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW |
| | COMMENTS. |
| | |
| | 1. SHEET P1.1A PLAN KEYED NOTES DESCRIPTION #8 EW-1: |
| | THE REFERENCE STANDARD FOR THE MIXING VALVE ANSI Z358.1 |
| | DOES NOT COMPLY WITH THE FBC-2004 PLUMBING . PLEASE |
| | KNOW THAT TEMPERATURE-ACTUATED MIXING VALVES, WHICH ARE |
| | INSTALLED TO REDUCE WATER TEMPERATURE TO DEFINED |
| | LIMITS, SHALL COMPLY WITH ASSE 1017. PER FBC-2004 |
| | PLUMBING SECTION 613.1 TEMPERATURE-ACTUATED MIXING |
| | VALVES. |
| | |
| | **RESPONSE NOTED, HOWEVER THE COMMENT HAS NOT BEEN |
| | ADDRESSED. RESPONSE STATES THAT THE MIXING VALVES TO |
| | THE HAND SINKS HAVE BEEN REMOVED, HOWEVER THE ORIGINAL |
| | COMMENT WAS ABOUT THE MIXING VALVE FOR THE EYE WASH NOT |
| | THE HAND SINKS. PLEASE REVISE PLANS FOR THE EYE WASH |
| | MIXING VALVE TO READ STANDARD ASSE 1017. PER FBC-2004 |
| | PLUMBING SECTION 613.1 TEMPERATURE-ACTUATED MIXING |
| | VALVES. |
| | |
| | **THE FOLLOWING IS A NEW COMMENT** |
| | |
| | 2. SHEET P1.1B WATER HEATER INSTALLATION DETAIL #1: THE |
| | EXPANSION TANK NEEDS TO BE DOWNSTREAM OF THE WATTS 200 |
| | SERIES PRESSURE REGULATOR VALVE. PER FBC-2004 PLUMBING |
| | SECTION 607.3.1 PRESSURE-REDUCING VALVE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE |
| | OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW |
| | PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |