| 2008-10-07 12:57:25 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | THE FOLLOWING COMMENTS ARE FROM THE PREVIOUS REVIEW |
| | DATED 8/13/08 AND HAVE NOT BEEN PROPERLY RESPONDED TO. |
| | |
| | 1} THE MINIMUM CURRENT CODES ARE NOT INDICATED ON THE |
| | ELECTRICAL SHEETS. |
| | |
| | 3} THE LIGHTING CONTROL PANEL OR AUTOMATED LIGHTING |
| | CONTROLS COULD NOT BE LOCATED ON THE PLANS. |
| | |
| | 4} NO LIGHTING PERFORMANCE CALCULATIONS WERE GIVEN, |
| | ONLY FIXTURE WATTAGE PER TYPE.***ALL THAT IS REQUIRED |
| | FOR THE ELECTRICAL REVIEW IS THE BASIC PRESCRIPTIVE |
| | REQUIREMENTS. SEE 13-415.2.ABC.1 PERFORMANCE |
| | CALCULATION PROCEDURES, GENERAL. |
| | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| | METHOD DESCRIBED IN SECTION 415.2.B.1. THE INSTALLED |
| | INTERIOR LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH |
| | SECTION 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR |
| | LIGHTING POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH |
| | SECTION 415.2.C.1 OR 415.2.B.1. THIS CAN BE |
| | DEMONSTRATED ON THE PLANS INDICATING THE WATTAGES OF |
| | THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE |
| | DENSITY REQUIREMENTS. INDICATE WATTAGES ON THE FIXTURE |
| | SCHEDULE TO CORRELATE WITH THE ONES IN THE |
| | CALCULATIONS. |
| | |
| | 6} THE RISER ON E2.1A STILL HAS AN EQUIPMENT GROUNDING |
| | CONDUCTOR RUNNING FROM THE TAP FEEDER TO THE NEW 200 |
| | AMP PANEL***250.6.THIS GROUND WOULD BE REQUIRED AFTER |
| | THE FIRST MEANS OF DISCONNECT PER 250.122. SEE COMMENT |
| | #1 BELOW. |
| | |
| | NEW COMMENTS THIS REVIEW 10/7/08. |
| | |
| | 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED |
| | PER 230.70. INDICATE LOCATION ON PLAN PER 230.72(A)(1). |
| | THE AHJ HAS DETERMINED THAT "NEAREST POINT OF ENTRANCE" |
| | SHALL BE NO FARTHER THAN 8' OF UNPROTECTED CONDUCTORS. |
| | INDICATE COMPLIANCE WITH THIS ARTICLE ON THE PLAN. |
| | |
| | 2} LABEL NEW PANEL LP-4 ON THE RISER DIAGRAM, SHEET |
| | E2.1A. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW. |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |