| 2008-08-13 11:46:08 | |
| | ** DENIED PLANS.** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| | THE FOLLOWING MINIMUM CODES. |
| | FBC 2004 W/ 2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE INCLUDE MINIMUM LEVELS FOR ANY NEW |
| | HORN/STROBE DEVICES PER FBC 11-4.28.1,.2 AND .3 (4) FOR |
| | ADA. |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | FOR AUTOMATED LIGHTING CONTROLS REQUIRED. STATING ON |
| | PLANS MOTION SENSOR OR STANDARD SWITCH DOES NOT MEET |
| | THE MINIMUM PER CODE. |
| | |
| | 4) NOTE: PLEASE INDICATE THE LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | |
| | 5) NOTE: PLANS SEEM TO BE SIGNED WITH SOME SORT OF |
| | INITIAL. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | DESIGN PROFESSIONAL PLEASE SUBMIT A SIGNED, DATED AND |
| | SEALED LETTER FOR SIGNATURE VERIFICATION. THIS LETTER |
| | NEEDS TO BE ORIGINAL AND NOTARIZED PER FS 117.05. |
| | FS 471.025 |
| | |
| | 6) NOTE: RISER SHOWS EQUIPMENT GROUNDING CONDUCTOR |
| | BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT |
| | PERMITTED. |
| | 250.6,250.24. THIS CREATES OBJECTIONABLE CURRENTS. |
| | |
| | 7) NOTE: PLEASE SEE NEW MECHANICAL COMMENTS AS THE |
| | COOLING LOAD CALCULATIONS WHICH ARE RAISED SEALS OVER A |
| | PHOTO-COPIED SIGNATURE WHICH IS IN VIOLATION OF FS |
| | 471.025, FAC 61G15-23.002 |
| | |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |