| 2008-08-06 16:53:16 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} MDP-1 IS LISTED AS MLO AND MDP-II IS LISTED AS MCB, |
| | SHEET E2.1A, THE RISER SHOWS MDP-1 AS HAVING THE 1200 |
| | AMP MAIN BREAKER. SHEET E1.2A NOTE #1 INDICATES THE |
| | MAIN DISCONNECT OUTSIDE AT THE METER LOCATION, PLEASE |
| | CORRELATE. |
| | |
| | 2} INDICATE COMPLIANCE WITH THE POWER DENSITY |
| | REQUIREMENTS OF CHAPTER 13 FBC. THE INTERIOR LIGHTING |
| | POWER ALLOWANCE FOR A BUILDING OR A SEPARATELY METERED |
| | OR PERMITTED PORTION OF A BUILDING SHALL BE DETERMINED |
| | BY EITHER THE BUILDING AREA METHOD DESCRIBED IN SECTION |
| | 415.2.C.1 OR THE SPACE-BY-SPACE METHOD DESCRIBED IN |
| | SECTION 415.2.B.1. TRADE-OFFS OF INTERIOR LIGHTING |
| | POWER ALLOWANCE AMONG PORTIONS OF THE BUILDING FOR |
| | WHICH A DIFFERENT METHOD OF CALCULATION HAS BEEN USED |
| | ARE NOT PERMITTED. THE INSTALLED INTERIOR LIGHTING |
| | POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| | 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION |
| | 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE |
| | PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN |
| | FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |