2008-08-06 12:00:20PLUMBING PLAN REVIEW:
 DENIED, NOTE **FOR PLAN REVIEW ONLY NOT FOR PERMIT**:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P1: PLEASE CORRELATE THE BRANCH DRAINS TO THE
 PEDICURE SPA. THE PLUMBING SANITARY PLAN INDICATES 2"
 FOR THE DRAIN, HOWEVER THE SANITARY ISOMETRIC RISER IS
 INDICATING 3". PER FBC-2004 PLUMBING SECTION 701.1
 SCOPE.
  
 2. SHEET P1 SANITARY ISOMETRIC RISER DIAGRAM: PLEASE
 CORRECT THE FOLLOWING ITEMS PER THE FBC-2004 PLUMBING
 SECTIONS.
  
 A} CLEARLY INDICATE THE SIZE FOR ALL WAST PIPING AND
 WATER-SEAL FIXTURE TRAPS. NOTE THE WASHING MACHINE
 STACK AND WATER-SEAL TRAP ARE NOT SIZED (WASHING
 MACHINE STACK SHALL BE 3" AND THE TRAP SHALL BE 2", PER
 SECTION 406.3) AS WELL AS THE WATER-SEAL TRAPS FOR THE
 LAVATORIES AND DRINKING FOUNTAIN ARE NOT SIZED (MINIMUM
 SIZE TRAP FOR THE LAVS AND DRINKING FOUNTAIN IS 1-1/4",
 PER TABLE 709.1). PER SECTION 701.1 SCOPE AND (W.P.B.
 AS AMENDED) SECTION 106.3.5.1.3 PLUMBING (13).
  
 B} CLEARLY INDICATE THAT THE PEDICURE SPA CHAIRS AS
 BEING DRAINED INDIRECTLY INTO EITHER A FLOOR SINK OR
 HUB DRAIN. PER SECTION 801.1 SCOPE, SECTION 802.2.2 AIR
 BREAK, SECTION 802.3 WASTE RECEPTORS, AND SECTION
 802.3.2 OPEN HUB WASTE RECEPTOR.
  
 C} CLEARLY INDICATE THE STUDER VENT (AIR ADMITTANCE
 VALVE OR A.A.V.) TO BE 4" ABOVE THE HORIZONTAL BRANCH
 DRAIN OF FIXTURE DRAIN BEING VENTED. PER SECTION 917.4
 LOCATION.
  
 D} CLEARLY INDICATE THE STUDER VENT (A.A.V.) TO BE 2"
 NOT 2: PER SECTION 901.1 SCOPE.
  
 E} CLEARLY INDICATE THAT THE STUDOR VENT (A.A.V.)
 SHALL BE PROVIDED WITH ACCESS AND THAT THE VALVE IS
 LOCATED WITHIN A VENTILATED SPACE THAT ALLOWS AIR TO
 ENTER THE VALVE. IT APPEARS THAT THE A.A.V. IS LOCATED
 IN THE PLUMBING CHASE. PER SECTION 917.5 ACCESS AND
 VENTILATION.
  
 3. SHEET P1 PLUMBING SANITARY PLAN INDICATES THE 3/4"
 P & T DRAIN TO MS. WHAT IS A MS? MS IS NOT INDICATED ON
 SHEET A1.01 OR P2 ABBREVIATIONS, PLEASE CLARIFY THIS.
 PLEASE NOTE THAT SHEET P2 CLEARLY INDICATES THE P & T
 VALVE TERMINATION TO THE EXTERIOR OF BUILDING. PER
 SECTION 501.1 SCOPE AND SECTION504.6.1 DISCHARGE.
  
 4. SHEET P2 PLUMBING SPECIFICATIONS NOTE #8 STATES THE
 FOLLOWING "ALL OTHER FIXTURES & SUPPLIES TO HAVE AIR
 CHAMBERS" PLEASE KNOW THAT AIR CHAMBERS ARE NOT
 APPROVED BY THE FBC-2004 PLUMBING CODE SECTION 604.9
 WATER HAMMER AND SHOULD BE DELETED FROM THE
 RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]