Plan Review Notes
Plan Review Notes For Permit 08070710
Permit Number 08070710
Review Stop E
Sequence Number 5
Notes
Date Text
2009-05-07 08:44:04**DENIED PLANS**
  
  
  
 1) NOTE: PLEASE SEE THE TITLE BLOCKS WHICH INDICATE A
 REVISION #6 HOWEVER THE PLANS ARE NOT LABELED WITH ANY
 REVISION #6.
 PLEASE COORDINATE ALL PLANS AND REVISIONS.
 FBC 106.1.1, 106..5 FOR CLARITY AND COORDINATION OF
 RECORD PLANS.
 NEC 2005 AS THERE ARE REVISIONS TO PLANS WHICH ARE NOT
 IDENTIFIED. SEE COMMENT #2.
  
 2) NOTE: PLANS NOW INDICATE AN EXISTING EMERGENCY LIGHT
 FIXTURE TO REMAIN. PLEASE INDICATE WHERE THE
 DISCONNECTING MEANS OF THIS BASE BUILDING BRANCH
 CIRCUIT IS LOCATED. IT IS BEING *ASSUMED* THIS IS PART
 OF THE BASE BUILDING CIRCUIT AS IT WAS REQUIRED TO BE
 INSTALLED BECAUSE IT WAS A SHELL SPACE ON ORIGINAL
 PLANS. THE FIXTURES AND WIRING WHICH WERE INSTALLED FOR
 SHELL SPACES WERE TO BE REMOVED OR BE CONTROLLED FROM
 TENANT SPACE ELECTRICAL SYSTEMS. IS THIS ELECTRICAL IN
 ONE TENANT SPACE FED FROM TWO COMPLETELY SEPARATE
 SERVICES?
 THIS IS A HAZARD IF THIS IS INDEED HOW THIS IS
 INSTALLED AND WIRED.
 PLEASE REVISE PLANS AND CLEAR UP WHAT THE DESIGN IS
 BEING PROPOSED. AS NOTED ABOVE, THE EMERGENCY LIGHT
 FIXTURES PLANS ON ORIGINAL SHELL TENANT SPACES WERE
 REQUIRED ONLY TO BE FED FROM BASE BUILDING UNTIL
 SEPARATE TENANTS WHICH ARE FED FROM A SEPARATE SERVICE
 ARE BUILT OUT.
 240.24B, 210.25
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  