| 2009-05-07 08:44:04 | **DENIED PLANS** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE TITLE BLOCKS WHICH INDICATE A |
| | REVISION #6 HOWEVER THE PLANS ARE NOT LABELED WITH ANY |
| | REVISION #6. |
| | PLEASE COORDINATE ALL PLANS AND REVISIONS. |
| | FBC 106.1.1, 106..5 FOR CLARITY AND COORDINATION OF |
| | RECORD PLANS. |
| | NEC 2005 AS THERE ARE REVISIONS TO PLANS WHICH ARE NOT |
| | IDENTIFIED. SEE COMMENT #2. |
| | |
| | 2) NOTE: PLANS NOW INDICATE AN EXISTING EMERGENCY LIGHT |
| | FIXTURE TO REMAIN. PLEASE INDICATE WHERE THE |
| | DISCONNECTING MEANS OF THIS BASE BUILDING BRANCH |
| | CIRCUIT IS LOCATED. IT IS BEING *ASSUMED* THIS IS PART |
| | OF THE BASE BUILDING CIRCUIT AS IT WAS REQUIRED TO BE |
| | INSTALLED BECAUSE IT WAS A SHELL SPACE ON ORIGINAL |
| | PLANS. THE FIXTURES AND WIRING WHICH WERE INSTALLED FOR |
| | SHELL SPACES WERE TO BE REMOVED OR BE CONTROLLED FROM |
| | TENANT SPACE ELECTRICAL SYSTEMS. IS THIS ELECTRICAL IN |
| | ONE TENANT SPACE FED FROM TWO COMPLETELY SEPARATE |
| | SERVICES? |
| | THIS IS A HAZARD IF THIS IS INDEED HOW THIS IS |
| | INSTALLED AND WIRED. |
| | PLEASE REVISE PLANS AND CLEAR UP WHAT THE DESIGN IS |
| | BEING PROPOSED. AS NOTED ABOVE, THE EMERGENCY LIGHT |
| | FIXTURES PLANS ON ORIGINAL SHELL TENANT SPACES WERE |
| | REQUIRED ONLY TO BE FED FROM BASE BUILDING UNTIL |
| | SEPARATE TENANTS WHICH ARE FED FROM A SEPARATE SERVICE |
| | ARE BUILT OUT. |
| | 240.24B, 210.25 |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |