Text |
| 2008-12-26 11:51:29 | ** PROVISO** |
| | |
| | 1) NOTE: THE FIXTURE TYPES AND NUMBER OF FIXTURES HAVE |
| | NOW BEEN REVISED. THE LIGHTING CALCULATION TABLE NOW |
| | INDICATE AN ADDITIONAL ALLOWANCE FOR DISPLAY AREAS. |
| | HOWEVER PLEASE SEE 13-415.2.B.2. THE FOLLOWING IS |
| | EXTRACTED DIRECTLY FROM THE CODE. THIS IS NOT A RETAIL |
| | OCCUPANCY. |
| | |
| | ** |
| | FOR LIGHTING EQUIPMENT INSTALLED IN RETAIL SPACES THAT |
| | IS SPECIFICALLY DESIGNED AND DIRECTED TO HIGHLIGHT |
| | MERCHANDISE, PROVIDED THAT THE ADDITIONAL LIGHTING |
| | POWER SHALL NOT EXCEED: |
| | (1) 1.6 WATTS PER SQUARE FOOT TIMES THE AREA OF |
| | SPECIFIC DISPLAY OR |
| | ** |
| | |
| | ** PLEASE REVISE TO REMOVE ADDITIONAL ALLOWANCES. |
| | |
| | PLEASE SEE THE FIXTURE LEGEND WHICH GIVES THE FIXTURE |
| | COUNT AND WATTAGES. THERE ARE MORE TYPE *C* FIXTURES ON |
| | PLANS THAN ON TABLE. THE TOTAL ALLOWANCE BASED ON THIS |
| | SPACE AND OCCUPANCY IS 2596. THE DESIGN WATTAGE WHICH |
| | IS BASED ON FIXTURES ON PLANS AND WATTAGES SHOWN IS |
| | 2584. |
| | AS THIS DOES NOT EXCEED ALLOWANCE PER THE FBC A PROVISO |
| | TO REVISE PLANS AT LATER DATE IS GIVEN. |
| | ** IF THERE ARE OTHER REVISIONS PLEASE REVISE BEFORE |
| | ROUGH. IF THESE BECOME THE ONLY REVISED ITEM PLEASE |
| | REVISE BEFORE FINAL. |
| | |
| | 13-415.2,13-415.2.ABC.1.1, .1.2. ETC |
| | |
| | 2) NOTE: SIGN REQUIRED FOR DOORS AT TRANSFORMER |
| | LOCATION. |
| | |
| | *ELECTRICAL ROOM/ NO STORAGE* |
| | |
| | OR WORDS TO THAT AFFECT. 240.24,110.26 |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |