2008-12-26 11:51:29** PROVISO**
  
 1) NOTE: THE FIXTURE TYPES AND NUMBER OF FIXTURES HAVE
 NOW BEEN REVISED. THE LIGHTING CALCULATION TABLE NOW
 INDICATE AN ADDITIONAL ALLOWANCE FOR DISPLAY AREAS.
 HOWEVER PLEASE SEE 13-415.2.B.2. THE FOLLOWING IS
 EXTRACTED DIRECTLY FROM THE CODE. THIS IS NOT A RETAIL
 OCCUPANCY.
  
 **
 FOR LIGHTING EQUIPMENT INSTALLED IN RETAIL SPACES THAT
 IS SPECIFICALLY DESIGNED AND DIRECTED TO HIGHLIGHT
 MERCHANDISE, PROVIDED THAT THE ADDITIONAL LIGHTING
 POWER SHALL NOT EXCEED:
 (1) 1.6 WATTS PER SQUARE FOOT TIMES THE AREA OF
 SPECIFIC DISPLAY OR
 **
  
 ** PLEASE REVISE TO REMOVE ADDITIONAL ALLOWANCES.
  
 PLEASE SEE THE FIXTURE LEGEND WHICH GIVES THE FIXTURE
 COUNT AND WATTAGES. THERE ARE MORE TYPE *C* FIXTURES ON
 PLANS THAN ON TABLE. THE TOTAL ALLOWANCE BASED ON THIS
 SPACE AND OCCUPANCY IS 2596. THE DESIGN WATTAGE WHICH
 IS BASED ON FIXTURES ON PLANS AND WATTAGES SHOWN IS
 2584.
 AS THIS DOES NOT EXCEED ALLOWANCE PER THE FBC A PROVISO
 TO REVISE PLANS AT LATER DATE IS GIVEN.
 ** IF THERE ARE OTHER REVISIONS PLEASE REVISE BEFORE
 ROUGH. IF THESE BECOME THE ONLY REVISED ITEM PLEASE
 REVISE BEFORE FINAL.
  
 13-415.2,13-415.2.ABC.1.1, .1.2. ETC
  
 2) NOTE: SIGN REQUIRED FOR DOORS AT TRANSFORMER
 LOCATION.
  
 *ELECTRICAL ROOM/ NO STORAGE*
  
 OR WORDS TO THAT AFFECT. 240.24,110.26
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved