| 2008-12-12 16:37:11 | REVIEW #: 3RD |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. **PARTIALLY ADDRESSED** PLEASE PLACE SHOP DRAWING |
| | REVIEW STAMPS ON FRONT OF PAGES FOR RECORDS RETENTION |
| | PURPOSES. THSES PLANS WILL BE DIGITIZED FOR ARCHIVING |
| | AND STAMPS ON BACKS OF PAGES WILL NOT BE RECORDED. |
| | ALSO, PAGE M1 CONTAINS A SHOP DRAWING REVIEW STAMP |
| | DATED 10/25/08 BUT THE PLANS INDICATE THEY WERE REVISED |
| | ON 11/25/08 (SAME GOES FOR ENGINEER'S SEAL AND |
| | SIGNATURE). HOW IS THIS POSSIBLE? PLEASE CORRECT DATES |
| | ON PLANS TO CORRESPOND WITH ACTUAL REVISION DATES. |
| | |
| | 2. OK |
| | |
| | 3. **NOT ADDRESSED** PAGE M1 DUCT TAKEOFF DETAIL: IN NO |
| | CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT THAT |
| | IS IN DIRECT CONTACT WITH IT BE LESS THAN 1.5 INCHES |
| | WIDE IN ACCORDANCE WITH FBCM 603.5.6.6. |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | 6. **NOT ADDRESSED** PAGE M1 PLUMBING NOTE #18: THIS |
| | NOTE CALLS FOR PVC O BE USED FOR THE CONDENSATE DRAIN |
| | LINE. PVC MAY NOT BE USED IN THE MECHANICAL ROOM WHICH |
| | ALSO SERVES AS A RETURN AIR PLENUM. MATERIALS EXPOSED |
| | WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E 84 PER FBCM 602.2.1. |
| | |
| | 7. OK |
| | |
| | 8. **NOT ADDRESSED** PAGE A.1 SHOWS A SINGLE DOOR IN |
| | MECHANICAL ROOM 204. PAGE M1 FLOOR PLAN SHOWS A |
| | LOUVERED DOUBLE-DOOR AT THIS LOCATION. WHICH IS |
| | CORRECT? NO DOOR SCHEDULE COULD BE FOUND IN THE |
| | ARCHITECTURAL PLANS TO SHOW WHICH TYPE OF DOOR IS TO BE |
| | USED AT THIS LOCATION. PLEASE SHOW THE DOOR TYPES TO |
| | VERIFY THAT A LOUVERED DOOR IS BEING PROVIDED FOR |
| | RETURN AIR. ALSO, THE TYPE OF DOOR SHALL MEET THE |
| | REQUIREMENTS FOR A PLENUM IN ACCORDANCE WITH FBCM |
| | 602.2.1. |
| | |
| | 9. SEE ABOVE. |
| | |
| | 10. OK |
| | |
| | 11. OK |
| | |
| | **NEW** THESE PLANS HAVE FAILED REVIEW FOR CODE |
| | COMPLIANCE 3 TIMES. EACH TIME COMMENTS 3, 6 AND 8 ABOVE |
| | HAVE BEEN REPEATED AND HAVE NOT BEEN ADDRESSED OR |
| | CORRECTED ON PLANS. AS A RESULT, A FINE OF FOUR TIMES |
| | THE PLAN REVIEW FEE IS BEING IMPOSED ON THIS PERMIT |
| | APPLICATION IN ACCORDANCE WITH FS 553.80(2)(B). THE |
| | CITY OF WEST PALM BEACH ATTRIBUTES 30% OF PERMIT FEES |
| | TO PLAN REVIEW. THE PERMIT FEE IS $800. THIRTY PERCENT |
| | OF THAT FEE (THE PLAN REVIEW FEE) IS $240. THE TOTAL |
| | AMOUNT DUE PRIOR TO RESUBMISSION OF PLANS FOR PERMIT IS |
| | $960.00. |
| | |