Plan Review Notes
Plan Review Notes For Permit 08070710
Permit Number 08070710
Review Stop E
Sequence Number 3
Notes
Date Text
2008-12-12 08:35:11*** PER PREVIOUS NOTICE TO REPEAT COMMENTS FOR CODE
 COMPLIANCE, THE CODE SECTIONS WERE REPEATED THREE OR
 MORE TIMES. THE CODE SECTIONS FOR FBC CHAPTER 13 FOR
 LIGHTING COMPLIANCE ALONG WITH OTHER SECTIONS WERE
 REPEATED AND COMPLIANCE HAS STILL NOT BEEN ACHEIVED. TH
 IS A STATUTORY REQUIREMENT AND IS REQUIRED. THIS IS NOT
 AN OPTIONAL FEE TO BE ASSESED. THE AMOUNT OF $960 WILL
 BE DUE.
 ONE COPY OF ELECTRICAL PLANS WERE RETAINED BY THIS
 OFFICE AS REQUIRED.
2008-12-09 10:48:20 
 ** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE BE SURE ALL SETS ARE PLACED TOGETHER IN
 COMPLETE SETS WHEN RESUBMITTING. PLEASE REMOVE ANY
 OLD/VOIDED SHEETS.
  
 2) NOTE: PLANS SUBMITTED WHICH WERE REVISED ON 11/25/08
 ARE ACTUALLY SIGNED, DATED AND SEALED WITH A DATE OF
 10/25/08. THIS IS NOT POSSIBLE.
 FS 471.025
  
 3) NOTE: PLANS SHALL CONTAIN THE * SHOP DRAWING REVIEW
 STAMP* AND SIGNATURE OF THE BASE BUILDING DESIGNERS OF
 RECORD ON EACH AND EVERY SHEET. THIS IS REQUIRED TO BE
 ON THE PLANS AND NOT ON THE BACK OF THE SHEETS. RECORD
 PLANS ARE SCANNED AND SCANNING OF THE BACK OF THE
 SHEETS WHICH ARE *BLANK* DOES NOT SHOW ACTUAL RECORD OF
 ANYTHING.
 PLEASE ALSO BE SURE THESE STAMPS ARE SIGNED BY THE
 RESPONSIBLE DESIGNER OF RECORD. THE SIGNATURES FOR BOTH
 PERSONS AS STAMPED ARE NOT FROM THE DESIGNERS OF
 RECORD.
 FS481.221,471.025
  
 4) NOTE: PLEASE SEE 13-415.2, 13-415.2.ABC.1.1,.1.2 FOR
 LIGHTING POWER ALLOWANCES. THE AMOUNT OF FIXTURES AND
 WATTAGE ON PLANS EXCEEDS MAXIMUM ALLOWANCE UNDER THE
 ENERGY CODE. PLEASE SEE EXAMPLES SUCH AS FIXTURE *A*.
 THE AMOUNT OF FIXTURES ON PLANS IS GREATER THAN THE
 AMOUNT IN THE CALCULATIONS. THIS IS ONE FIXTURE AND
 THERE ARE OTHERS WHICH ARE OVER. THE DESIGN WATTAGE ON
 PLANS COMES TO OVER 3000 WATTS WHEN ALLOWANCE BASED ON
 THE 1236 SQ FT IS 2595.
  
 5) NOTE: PLEASE SEE 11-4.28.3(4). PLANS NOTE THE STROBE
 75 FLASH RATE. THIS SHOULD BE 75CD/ OR CANDELA. THE
 FLASH RATE IS DIFFERENT.
  
 6) NOTE: PLEASE BE SURE THE SUITE OR UNIT NUMBER IS
 LISTED ON THE TITLE BLOCKS OF EACH SHEET. THIS CAN BE
 PRINTED ON ANY SHEETS WHICH DO NOT NEED TO BE REVISED.
 FAC 61G1-16.004, 61G15-23.002, FBC 106.5.
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  