Plan Review Notes
Plan Review Notes For Permit 08070710
Permit Number 08070710
Review Stop M
Sequence Number 2
Notes
Date Text
2008-11-15 15:56:30REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS APPLICATION IS FOR A TENANT IMPROVEMENT IN A
 BUILDING WHICH IS NOT YET COMPLETED. IF THIS PERMIT IS
 TO BE ISSUED PRIOR TO C.O. OF THE BASE BUILDING, THE
 DESIGNERS F THE BASE BUILDING SHALL PERFORM A SHOP
 DRAWING REVIEW OF THESE PLANS AND APPROVE THEM IN
 WRITING (SHOP DRAWING REVIEW STAMP). THIS IS TO ENSURE
 THAT THE BASE BUILDING DESIGNERS ARE AWARE OF ANY
 CHANGES WHICH MAY BE MADE THAT WILL ALTER THE BASE
 BUILDING DESIGN OR PLANS PRIOR TO FINAL INSPECTIONS. IN
 ADDITION, ANY NEW INFORMATION PROVIDED REGARDING ENERGY
 UTILIZING SYSTEMS IN THIS SPACE WILL NEED TO BE
 INCLUDED IN THE BASE BUILDING ENERGY CALCULATIONS AND
 SUBMITTED AS A REVISION PRIOR TO C.O. OF THE BASE
 BUILDING.
  
 2. OK
  
 3. **PARTIALLY ADDRESSED** PAGE M1 DUCT TAKEOFF DETAIL:
 IN NO CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT
 THAT IS IN DIRECT CONTACT WITH IT BE LESS THAN 1.5
 INCHES WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 4. OK
  
 5. OK
  
 6. **NOT ADDRESSED** PAGE M1 PLUMBING NOTE #18: THIS
 NOTE CALLS FOR PVC O BE USED FOR THE CONDENSATE DRAIN
 LINE. PVC MAY NOT BE USED IN THE MECHANICAL ROOM WHICH
 ALSO SERVES AS A RETURN AIR PLENUM. MATERIALS EXPOSED
 WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A
 FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A
 SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED
 IN ACCORDANCE WITH ASTM E 84 PER FBCM 602.2.1.
  
 7. OK
  
 8. **NOT ADDRESSED** PAGE A.1 SHOWS A SINGLE DOOR IN
 MECHANICAL ROOM 204. PAGE M1 FLOOR PLAN SHOWS A
 LOUVERED DOUBLE-DOOR AT THIS LOCATION. WHICH IS
 CORRECT? NO DOOR SCHEDULE COULD BE FOUND IN THE
 ARCHITECTURAL PLANS TO SHOW WHICH TYPE OF DOOR IS TO BE
 USED AT THIS LOCATION. PLEASE SHOW THE DOOR TYPES TO
 VERIFY THAT A LOUVERED DOOR IS BEING PROVIDED FOR
 RETURN AIR. ALSO, THE TYPE OF DOOR SHALL MEET THE
 REQUIREMENTS FOR A PLENUM IN ACCORDANCE WITH FBCM
 602.2.1.
  
 9. SEE ABOVE.
  
 10. OK
  
 11. OK
  