| Plan Review Notes For Permit 08070710 |
| Permit Number |
08070710 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-11-12 11:43:59 | ***DENIED*** | | | | | | 1) ON SHEET A.3- CAPTION 1, CLARIFY AS TO WHETHER THE | | | ADDRESS VERBAGE IS FOR BUILDING OR THE SUITE. A.3 CAN | | | NOT BE FOUND WITH INITIAL SUBMITTAL. | | | | | | 2) SHOW LAYOUT OF THE SPRINKLER HEADS FOR THE FLOOR | | | SPACE. THESE HEADS MAY BE SHOWN ON THE REFLECTED | | | CEILING PLAN. NO ATTACHED ENGINEERED SPRINKLER DRAWINGS | | | FOUND WITH THIS SUBMITTAL. | | | | | | PLANS DON'T SEEM TO CORRELATE WITH RESPONSE LETTER. | | | | | | | | | MIKE WENNERGREN, ASST. FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|