Plan Review Notes
Plan Review Notes For Permit 08070710
Permit Number 08070710
Review Stop E
Sequence Number 2
Notes
Date Text
2008-11-10 11:26:45 
  
  
 ** DENIED 2ND REVIEW **
  
  
  
 1) NOTE: SAME NOTE AS ON PREVIOUS REVIEW:
 THE BASE BUILDING DOES NOT HAVE A CERTIFICATE OF
 OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT PERMITTED
 BEFORE THE C OF O OF BASE BUILDING ARE TO CONTAIN A
 *SHOP DRAWING* REVIEW STAMP AND SIGNATURE FROM THE BASE
 BUILDING DESIGNERS OF RECORD ON EACH RELEVANT SHEET.
 THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL SUCH TIME A C OF O IS ISSUED.
 FS 471,481
  
 2) NOTE: SAME NOTE AS ON PREVIOUS REVIEW:
 PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR BUILD OUT
 BEFORE THE C OF O IS ISSUED ON BASE BUILDING WILL
 REQUIRE THE FOLLOWING TO BE REVISED.
 THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE
 REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS.
 220
 THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED
 FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS
 TO NEW KNOWN ENERGY USE.
 THIS INCLUDES ALL NEW LIGHTING.
 FBC CHAPTER 13.
  
 3) NOTE: THE PLANS STILL INDICATE EXISTING RETAIL
 HOWEVER THIS IS NOT POSSIBLE AS THE BUILDING CONTAINS
 *SHELL* SPACES FOR FUTURE. THE PLANS NEED TO BE
 ADJUSTED ACCORDINGLY.
 FBC 301.1
 FBC 106.1.1,106.5 FOR CLARITY, COORDINATION OF RECORD
 PLANS.
  
 4) NOTE: THE SUBMITTED LIGHTING PERFORMANCE
 CALCULATIONS ARE NOT COMPLETE AT THIS TIME. PLEASE SEE
 THE FIXTURE LEGEND NOW SUBMITTED IS NOT YET COMPLETE.
 AN EXAMPLE IS THE *Q* FIXTURE. THIS ONE EXAMPLE IS
 GIVEN AS A BENEFIT.
 PLEASE SEE SECTIONS OF CODE BELOW WHICH WERE GIVEN ON
 PREVIOUS REVIEW. PLEASE SEE TRACK LIGHTING IN THE FBC.
 THE CODE REQUIRES ANY LINE VOLTAGE FIXTURES TO BE
 FIGURED AT THE MAXIMUM VA PER FIXTURE OR 30VA PER
 LINEAR FT OF TRACK WHICH EVER IS GREATER. IF THESE ARE
 LOW VOLTAGE TYPES THEN THE VA IS BASED ON THE MAXIMUM
 VA OF THE TRANSFORMER. THE FIXTURE LEGEND AS SUBMITTED
 HAS A N/A NEXT TO FIXTURE AND ASSOCIATED EQUIPMENT.
  
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS IN
 COMPLIANCE WITH FBC 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 5) NOTE: THE RISER SHOWS WHAT APPEARS TO BE THE
 DISCONNECT AND TRANSFORMER WHICH WOULD BE LOCATED IN
 THE STORAGE CLOSET ON MEZZANINE LEVEL WHICH IS NOT
 PERMITTED.
 THE ELECTRICAL PLANS DO NOT SHOW EITHER OF THESE TWO ON
 MEZZANINE LEVEL AND ONLY SHOWS THE PANEL.
 PLEASE SHOW LOCATIONS OF ALL EQUIPMENT, LABEL
 ACCORDINGLY TO RISER AND PANEL IDENTIFICATION.
 PLEASE SEE 240.21,450.9,450.13,450.21, 240.24 ETC
 THIS AS SHOWN ON PLANS IS CLEARLY A STORAGE CLOSET
 WHICH WILL CONTAIN COMBUSTIBLES AND EASILY IGNITABLE
 MATERIALS. THIS IS A FIRE AND LIFE SAFETY HAZARD.
 PLEASE ADJUST, RE-LOCATE ETC.
  
 6) NOTE: FROM PREVIOUS REVIEW:
 PLEASE INCLUDE THE DEVICE LOCATIONS, LEVELS, AND
 HEIGHTS FOR ALL FIRE ALARM DEVICES FOR ADA COMPLIANCE.
 FBC 11-4.28.1,.2 AND .3.
  
 7) NOTE: PLEASE SEE 410.5, 410.6 ETC AS THE TYPE *Q*
 FIXTURE MAY NOT BE LOCATED NEAR COMBUSTIBLES.
  
 8) NOTE: PLEASE SEE NOTICE TOT FS 553.80(2)(B) IS GIVEN
 AT THIS TIME DUE TO SOME COMMENTS BEING REPEATED . THIS
 ONLY A NOTICE AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  