| 2008-11-10 11:26:45 | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: SAME NOTE AS ON PREVIOUS REVIEW: |
| | THE BASE BUILDING DOES NOT HAVE A CERTIFICATE OF |
| | OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT PERMITTED |
| | BEFORE THE C OF O OF BASE BUILDING ARE TO CONTAIN A |
| | *SHOP DRAWING* REVIEW STAMP AND SIGNATURE FROM THE BASE |
| | BUILDING DESIGNERS OF RECORD ON EACH RELEVANT SHEET. |
| | THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE |
| | BUILDING UNTIL SUCH TIME A C OF O IS ISSUED. |
| | FS 471,481 |
| | |
| | 2) NOTE: SAME NOTE AS ON PREVIOUS REVIEW: |
| | PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR BUILD OUT |
| | BEFORE THE C OF O IS ISSUED ON BASE BUILDING WILL |
| | REQUIRE THE FOLLOWING TO BE REVISED. |
| | THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE |
| | REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS. |
| | 220 |
| | THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED |
| | FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS |
| | TO NEW KNOWN ENERGY USE. |
| | THIS INCLUDES ALL NEW LIGHTING. |
| | FBC CHAPTER 13. |
| | |
| | 3) NOTE: THE PLANS STILL INDICATE EXISTING RETAIL |
| | HOWEVER THIS IS NOT POSSIBLE AS THE BUILDING CONTAINS |
| | *SHELL* SPACES FOR FUTURE. THE PLANS NEED TO BE |
| | ADJUSTED ACCORDINGLY. |
| | FBC 301.1 |
| | FBC 106.1.1,106.5 FOR CLARITY, COORDINATION OF RECORD |
| | PLANS. |
| | |
| | 4) NOTE: THE SUBMITTED LIGHTING PERFORMANCE |
| | CALCULATIONS ARE NOT COMPLETE AT THIS TIME. PLEASE SEE |
| | THE FIXTURE LEGEND NOW SUBMITTED IS NOT YET COMPLETE. |
| | AN EXAMPLE IS THE *Q* FIXTURE. THIS ONE EXAMPLE IS |
| | GIVEN AS A BENEFIT. |
| | PLEASE SEE SECTIONS OF CODE BELOW WHICH WERE GIVEN ON |
| | PREVIOUS REVIEW. PLEASE SEE TRACK LIGHTING IN THE FBC. |
| | THE CODE REQUIRES ANY LINE VOLTAGE FIXTURES TO BE |
| | FIGURED AT THE MAXIMUM VA PER FIXTURE OR 30VA PER |
| | LINEAR FT OF TRACK WHICH EVER IS GREATER. IF THESE ARE |
| | LOW VOLTAGE TYPES THEN THE VA IS BASED ON THE MAXIMUM |
| | VA OF THE TRANSFORMER. THE FIXTURE LEGEND AS SUBMITTED |
| | HAS A N/A NEXT TO FIXTURE AND ASSOCIATED EQUIPMENT. |
| | |
| | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS IN |
| | COMPLIANCE WITH FBC 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | |
| | 5) NOTE: THE RISER SHOWS WHAT APPEARS TO BE THE |
| | DISCONNECT AND TRANSFORMER WHICH WOULD BE LOCATED IN |
| | THE STORAGE CLOSET ON MEZZANINE LEVEL WHICH IS NOT |
| | PERMITTED. |
| | THE ELECTRICAL PLANS DO NOT SHOW EITHER OF THESE TWO ON |
| | MEZZANINE LEVEL AND ONLY SHOWS THE PANEL. |
| | PLEASE SHOW LOCATIONS OF ALL EQUIPMENT, LABEL |
| | ACCORDINGLY TO RISER AND PANEL IDENTIFICATION. |
| | PLEASE SEE 240.21,450.9,450.13,450.21, 240.24 ETC |
| | THIS AS SHOWN ON PLANS IS CLEARLY A STORAGE CLOSET |
| | WHICH WILL CONTAIN COMBUSTIBLES AND EASILY IGNITABLE |
| | MATERIALS. THIS IS A FIRE AND LIFE SAFETY HAZARD. |
| | PLEASE ADJUST, RE-LOCATE ETC. |
| | |
| | 6) NOTE: FROM PREVIOUS REVIEW: |
| | PLEASE INCLUDE THE DEVICE LOCATIONS, LEVELS, AND |
| | HEIGHTS FOR ALL FIRE ALARM DEVICES FOR ADA COMPLIANCE. |
| | FBC 11-4.28.1,.2 AND .3. |
| | |
| | 7) NOTE: PLEASE SEE 410.5, 410.6 ETC AS THE TYPE *Q* |
| | FIXTURE MAY NOT BE LOCATED NEAR COMBUSTIBLES. |
| | |
| | 8) NOTE: PLEASE SEE NOTICE TOT FS 553.80(2)(B) IS GIVEN |
| | AT THIS TIME DUE TO SOME COMMENTS BEING REPEATED . THIS |
| | ONLY A NOTICE AT THIS TIME. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |