Plan Review Notes
Plan Review Notes For Permit 08070710
Permit Number 08070710
Review Stop B
Sequence Number 2
Notes
Date Text
2008-11-07 07:49:42BUILDING PLAN REVIEW
 PERMIT: 08070710
 ADD: 480 HIBISCUS ST. #103
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-7-08
 REVIEW: 2ND
 ACTION: DENIED
  
 1) OK
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 ** PARTIALY ADDRESSED. PLEASE READ THE NOTE BELOW AND
 SUPPLY ALL THE INFORMATION REQUESTED.**
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD.
  
 **NOT ADDREDDED ON THE PLANS**
 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT
 BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING
 SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE
 DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET.
 THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE
 BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481.
 THE REVIEW STAMP IS MISSING ON PLANS.
  
 ** RESPONSE NOTED, HOWEVER IF THIS IS NEW CONSTRUCTION
 TO A SPACE OR BUILDING WHICH HAS NOT RECEIVE A
 CERTIFICATE OF OCCUPANCY, AN ALTERATION LEVEL IS NOT
 RREQUIRED. AT THIS TIME OF REVIEW A CERTIFICATE OF
 OCCUPANCY IS NOT ISSUED TO THIS BUILDING.**
 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS
 THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE
 AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A
 TWELVE MONTH PERIOD; FBC(EXISTING) 305.1. IS THIS THE
 CASE FOR THIS PROJECT? IF NOT PLEASE SEE SECTION 304 OF
 THE FBC (EXISTING) ALTERATION LEVEL 2.
  
 7) OK
 8) OK
  
 NEW:
 A) PROVIDE A DOOR SCHEDULE SHOWING THE TYPE AND SIZE OF
 DOORS TO BE INSTALLED AT THEIR RESPECTIVE LOCATION
 ALONG WITH THE INTERIOR FINISH SCHEDULE THE SHOW ALL
 WALL FINISHES. SHEET A.2 SHOWS TWO SINGLE HUNG DOORS
 ACCORDING TO DETAIL #3, HOWEVER, THERE ARE TWO DETAILS
 REFERENCING THE #3. ON SHEET M1 THE DOORS ARE SHOWN AS
 DOUBLE SWING DOORS. CLARIFY. THE DETAIL FOR THE DRYWALL
 CEILING ON THE FIRST FLOOR IS MISSING FROM THE PLANS.
  
 B) SHEET A.4 NOTE #10 INDICATES THE FINISH DRYWALL TO
 BE FINISHED WITH ENAMEL PAINT: THEN REFERS TO FINISH
 SCHEDULE WHICH WAS NOT SUBMITTED. FBC 1210.2 WALL
 WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE A
 SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF 4
 FEET ABOVE THE FLOOR. SHOW COMPLIANCE.
  
 C) SHEET A.2. PROVIDE DETAIL DRAWINGS SHOWING THE
 STRUCTURAL SUPPORT FOR THE SUSPENDED WOOD CEILING AND
 THE SUSPENDED TRACK LIGHTING. ADDITIONAL INFORMATION IS
 REQUIRED 106.1.2*
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  