| 2008-11-07 07:49:42 | BUILDING PLAN REVIEW |
| | PERMIT: 08070710 |
| | ADD: 480 HIBISCUS ST. #103 |
| | CONT: THE TOWER GROUP |
| | TEL: (954)476-3200 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 11-7-08 |
| | REVIEW: 2ND |
| | ACTION: DENIED |
| | |
| | 1) OK |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | ** PARTIALY ADDRESSED. PLEASE READ THE NOTE BELOW AND |
| | SUPPLY ALL THE INFORMATION REQUESTED.** |
| | 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE |
| | 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO |
| | BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE |
| | LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4. |
| | PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION |
| | FOR THE UNIFORM AND CONCENTRATED LOAD. |
| | |
| | **NOT ADDREDDED ON THE PLANS** |
| | 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE |
| | A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT |
| | BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING |
| | SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE |
| | DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET. |
| | THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE |
| | BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481. |
| | THE REVIEW STAMP IS MISSING ON PLANS. |
| | |
| | ** RESPONSE NOTED, HOWEVER IF THIS IS NEW CONSTRUCTION |
| | TO A SPACE OR BUILDING WHICH HAS NOT RECEIVE A |
| | CERTIFICATE OF OCCUPANCY, AN ALTERATION LEVEL IS NOT |
| | RREQUIRED. AT THIS TIME OF REVIEW A CERTIFICATE OF |
| | OCCUPANCY IS NOT ISSUED TO THIS BUILDING.** |
| | 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS |
| | THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE |
| | AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A |
| | TWELVE MONTH PERIOD; FBC(EXISTING) 305.1. IS THIS THE |
| | CASE FOR THIS PROJECT? IF NOT PLEASE SEE SECTION 304 OF |
| | THE FBC (EXISTING) ALTERATION LEVEL 2. |
| | |
| | 7) OK |
| | 8) OK |
| | |
| | NEW: |
| | A) PROVIDE A DOOR SCHEDULE SHOWING THE TYPE AND SIZE OF |
| | DOORS TO BE INSTALLED AT THEIR RESPECTIVE LOCATION |
| | ALONG WITH THE INTERIOR FINISH SCHEDULE THE SHOW ALL |
| | WALL FINISHES. SHEET A.2 SHOWS TWO SINGLE HUNG DOORS |
| | ACCORDING TO DETAIL #3, HOWEVER, THERE ARE TWO DETAILS |
| | REFERENCING THE #3. ON SHEET M1 THE DOORS ARE SHOWN AS |
| | DOUBLE SWING DOORS. CLARIFY. THE DETAIL FOR THE DRYWALL |
| | CEILING ON THE FIRST FLOOR IS MISSING FROM THE PLANS. |
| | |
| | B) SHEET A.4 NOTE #10 INDICATES THE FINISH DRYWALL TO |
| | BE FINISHED WITH ENAMEL PAINT: THEN REFERS TO FINISH |
| | SCHEDULE WHICH WAS NOT SUBMITTED. FBC 1210.2 WALL |
| | WITHIN 2 FEET OF URINALS AND WATER CLOSETS SHALL HAVE A |
| | SMOOTH, HARD, NONABSORBENT SURFACE, TO A HEIGHT OF 4 |
| | FEET ABOVE THE FLOOR. SHOW COMPLIANCE. |
| | |
| | C) SHEET A.2. PROVIDE DETAIL DRAWINGS SHOWING THE |
| | STRUCTURAL SUPPORT FOR THE SUSPENDED WOOD CEILING AND |
| | THE SUSPENDED TRACK LIGHTING. ADDITIONAL INFORMATION IS |
| | REQUIRED 106.1.2* |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |