Plan Review Notes
Plan Review Notes For Permit 08070710
Permit Number 08070710
Review Stop M
Sequence Number 1
Notes
Date Text
2008-08-20 14:18:18REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THIS APPLICATION IS FOR A TENANT IMPROVEMENT IN A
 BUILDING WHICH IS NOT YET COMPLETED. IF THIS PERMIT IS
 TO BE ISSUED PRIOR TO C.O. OF THE BASE BUILDING, THE
 DESIGNERS F THE BASE BUILDING SHALL PERFORM A SHOP
 DRAWING REVIEW OF THESE PLANS AND APPROVE THEM IN
 WRITING (SHOP DRAWING REVIEW STAMP). THIS IS TO ENSURE
 THAT THE BASE BUILDING DESIGNERS ARE AWARE OF ANY
 CHANGES WHICH MAY BE MADE THAT WILL ALTER THE BASE
 BUILDING DESIGN OR PLANS PRIOR TO FINAL INSPECTIONS. IN
 ADDITION, ANY NEW INFORMATION PROVIDED REGARDING ENERGY
 UTILIZING SYSTEMS IN THIS SPACE WILL NEED TO BE
 INCLUDED IN THE BASE BUILDING ENERGY CALCULATIONS AND
 SUBMITTED AS A REVISION PRIOR TO C.O. OF THE BASE
 BUILDING.
  
 2. PROVIDE COOLING LOAD CALCULATIONS FOR THIS SPACE IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 3. PAGE M1 DUCT TAKEOFF DETAIL: HORIZONTAL DUCT SHALL
 BE SUPPORTED AT INTERVALS NOT GREATER THAN 5 FEET AND
 HANGERS, SADDLES AND OTHER SUPPORTS SHALL MEET THE DUCT
 MANUFACTURER?S RECOMMENDATIONS AND SHALL BE OF
 SUFFICIENT WIDTH TO PREVENT RESTRICTION OF THE INTERNAL
 DUCT DIAMETER. IN NO CASE SHALL THE MATERIAL SUPPORTING
 FLEXIBLE DUCT THAT IS IN DIRECT CONTACT WITH IT BE LESS
 THAN 1? INCHES WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 4. LOCATION OF CONDENSATE DISPOSAL NOT SHOWN ON PLANS.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
  
 5. PROVIDE AUXILIARY OR SECONDARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBCM 307.2.3.
  
 6. PAGE M1 PLUMBING NOTE #18: THIS NOTE CALLS FOR PVC O
 BE USED FOR THE CONDENSATE DRAIN LINE. PVC MAY NOT BE
 USED IN THE MECHANICAL ROOM WHICH ALSO SERVES AS A
 RETURN AIR PLENUM. MATERIALS EXPOSED WITHIN PLENUMS
 SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM
 E 84 PER FBCM 602.2.1.
  
 7. PAGE M1: NO INFORMATION WAS PROVIDED ON PLANS
 REGARDING THE CFM OF THE TOILET ROOM EXHAUST FAN.
 PROVIDE A FAN SCHEDULE WITH MAKE, MODEL, VOLTS, AMPS
 AND EXHAUST RATE EXPRESSED IN CFM. EXHAUST RATE SHALL
 BE IN COMPLIANCE WITH FBCM 403.4 AND ASHRAE 62.1-2004
 TABLE 6-4.
  
 8. PAGE A.1 SHOWS A SINGLE DOOR IN MECHANICAL ROOM 204.
 PAGE M1 FLOOR PLAN SHOWS A LOUVERED DOUBLE-DOOR AT THIS
 LOCATION. WHICH IS CORRECT? NO DOOR SCHEDULE COULD BE
 FOUND IN THE ARCHITECTURAL PLANS TO SHOW WHICH TYPE OF
 DOOR IS TO BE USED AT THIS LOCATION. PLEASE SHOW THE
 DOOR TYPES TO VERIFY THAT A LOUVERED DOOR IS BEING
 PROVIDED FOR RETURN AIR. ALSO, THE TYPE OF DOOR SHALL
 MEET THE REQUIREMENTS FOR A PLENUM IN ACCORDANCE WITH
 FBCM 602.2.1.
  
 9. PAGE M1 CALLS FOR A LOUVERED DOOR FOR RETURN AIR
 ABOVE THE DOOR IN MECHANICAL ROOM 204. NO SUCH DOOR IS
 SHOWN ON ARCHITECTURAL PLANS. SHOW THE LOCATION AND
 SIZE OF THE RETURN OPENING ON THE MECHANICAL PLANS. AIR
 DISTRIBUTION SYSTEMS SHALL BE DESIGNED AND INSTALLED TO
 PROVIDE THE REQUIRED DISTRIBUTION OF AIR IN ACCORDANCE
 WITH FBCM 603.1. ALSO, BALANCED RETURN IS REQUIRED IN
 ACCORDANCE WITH FBCM 601.4.
  
 10. THE OUTSIDE AIR INTAKE DUCT SHALL BE PROVIDED WITH
 AUTOMATIC SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH
 FBCB 13-409.1.ACB 3.3.
  
 11. THE OUTSIDE AIR CALCULATIONS DO NOT CORRESPOND WITH
 ASHRAE 62.1-2004 SECTION 6.2. EXAMPLE: THE OCCUPANCY
 SHOULD BE BASED ON A RETAIL OCCUPANCY ON TABLE 6-1.
 BASED ON THIS OCCUPANCY AND THE SIZE OF THE SPACE GIVEN
 ON THE PLANS, A MINIMUM VENTILATION RATE OF 227 CFM IS
 REQUIRED IN ACCORDANCE WITH FBCM 403.4 AND ASHRAE
 62.1-2004 SECTION 6.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]