| 2008-08-08 09:42:44 | |
| | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: THE BASE BUILDING DOES NOT HAVE A CERTIFICATE |
| | OF OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT |
| | PERMITTED BEFORE THE C OF O OF BASE BUILDING ARE TO |
| | CONTAIN A *SHOP DRAWING* REVIEW STAMP AND SIGNATURE |
| | FROM THE BASE BUILDING DESIGNERS OF RECORD ON EACH |
| | RELEVANT SHEET. |
| | THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE |
| | BUILDING UNTIL SUCH TIME A C OF O IS ISSUED. |
| | FS 471,481 |
| | |
| | 2) NOTE: PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR |
| | BUILD OUT BEFORE THE C OF O IS ISSUED ON BASE BUILDING |
| | WILL REQUIRE THE FOLLOWING TO BE REVISED. |
| | THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE |
| | REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS. |
| | 220 |
| | THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED |
| | FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS |
| | TO NEW KNOWN ENERGY USE. |
| | THIS INCLUDES ALL NEW LIGHTING. |
| | FBC CHAPTER 13. |
| | |
| | 3) NOTE: PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS IN |
| | PHOTO-METRICS ON STAIRS PER NFPA-101 2003, 7.8.1.3, |
| | 7.9.2.1, .2.2. |
| | |
| | 4) NOTE: PLEASE INDICATE ALL LIGHTING CONTROLS REQUIRED |
| | PER FBC 13-415.1.ABC.1.1,.1.2 AND .1.3. |
| | THE SYMBOL LEGEND DOES INDICATE SOME OCCUPANCY SENSOR |
| | TYPE DEVICES HOWEVER NONE OF THIS DEVICE S IS ON PLANS. |
| | IN FACT THE PLANS ONLY INDICATE STANDARD SWITCHING |
| | DEVICES WHICH ARE NOT PERMITTED. |
| | PLEASE PROVIDE ALL MAXIMUM TIMES ON ALL DEVICES. |
| | PLEASE BE SURE TO SEE NFPA-101 7.8.1.2.2 AND FBC |
| | 1006.1.2 AS ANY OCCUPANCY SENSOR FOR ANY EGRESS |
| | LIGHTING SHALL BE * FAIL SAFE ON*. |
| | |
| | 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS IN COMPLIANCE WITH FBC 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2. |
| | PLEASE SUBMIT THE FIXTURE SCHEDULE/LEGEND. |
| | PLEASE SEE THE SECTIONS OF THE CODE ABOVE. THE WATTAGE |
| | TO BE USED IS BASED ON THE FIXTURE WATTAGE NOT THE LAMP |
| | WATTAGE AS STATED ON PLANS. |
| | PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH A |
| | FIXTURE LEGEND ETC SOME OF THESE ITEMS FOR CODE |
| | COMPLIANCE CAN NOT BE DETERMINED AT THIS TIME. |
| | |
| | 6) NOTE: PLEASE PROVIDE VOLTAGE DROP PER |
| | 13-413.1.ABC.1.2 FOR CU. |
| | |
| | 7) NOTE: PLEASE COMPLETE PANEL SCHEDULE FOR ALL |
| | CIRCUITS TO SPECIFIC AREAS AND LOCATIONS. |
| | 408.4 |
| | |
| | 8) NOTE: PLEASE COORDINATE ALL CIRCUITS. PLEASE SEE ONE |
| | FOR EXAMPLE AS L-10 IS INDICATED ON PANEL SCHEDULE AS |
| | *MEZZANINE* YET THIS IS ALSO SHOWN ON PLANS TO THE |
| | REFRIGERATOR. |
| | NO DEDICATED CIRCUIT SHOWN FOR REFRIGERATOR. |
| | PLEASE SEE SOME OTHER CIRCUITS SHOWING A QUESTION MARK |
| | NEXT TO THE PANEL DESIGNATION ON PLAN. |
| | 408.4, 240.4, ETC |
| | |
| | 9) NOTE: PLEASE VERIFY RISER AS THE GUTTER IS INDICATED |
| | AS RAIN TIGHT? PLEASE ALSO INDICATE THE SIZE/AMPERAGE |
| | OF THE GUTTER PROVIDED. |
| | PLEASE INDICATE A FLOATING NEUTRAL ON THE NEW METER AS |
| | THE MAIN FOR TENANT SHOWN WILL BE AFTER A MEANS OF |
| | DISCONNECT FOR SERVICE. |
| | 250.24, 250.6 |
| | |
| | 10) NOTE: PLEASE SEE 600.5 AS THE LOAD FOR A SIGN |
| | CIRCUIT IS REQUIRED TO BE FIGURED AT 1200VA. THIS WOULD |
| | BE 10AMPS ON THE CIRCUIT. |
| | ** |
| | |
| | 11) NOTE: PLEASE SEE 210.62 FOR MISSING SHOW WINDOW |
| | RECEPTACLES. |
| | PLEASE ALSO SEE 220.43 |
| | |
| | 12) NOTE: PLEASE INCLUDE LOADS FOR TRACK LIGHTING PER |
| | 220.43 |
| | |
| | 13) NOTE: BASE BUILD OUT PLANS SHALL INCLUDE DEVICES TO |
| | COMPLY WITH THE FIRE CODES, SUCH AS NFPA-1, NFPA-72 AND |
| | FBC 2004 W/2007 REVISIONS. |
| | PLEASE SEE FBC 11-4.28 (ALL) AND INDICATE REQUIRED |
| | DEVICES ACCORDINGLY |
| | |
| | ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET ON |
| | DESIGN SHEETS THERE MAY VERY WELL BE NEW COMMENTS ON |
| | THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS |
| | TIME. |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |