 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} NOTE THAT HAND DRAWN CHANGES/NOTES TO THE PLAN ARE
 NOT ACCEPTABLE AS THEY CANNOT BE VERIFIED AS BEING MADE
 BY THE DESIGNER OF RECORD AS REQUIRED BY FS 471 OR 481,
 AS APPLICABLE.SHEET A.0
  
 ALL COMMENTS ARE FOR SHEET E.1
  
 2} THE FEED FROM THE DISCONNECT AT THE METER AND THE
 TRANSFORMER DISCONNECT DOES NOT INCLUDE AN EQUIPMENT
 GROUND. INDICATE IF THIS IS A METAL CONDUIT IF NOT
 INSTALL THE EQUIPMENT GROUND PER 250.122. ALSO INDICATE
 CONDUIT AND WIRE SIZE,TYPE AND NUMBER OF CONDUCTORS
 FROM THE 70 AMP TRANSFORMER DISCONNECT TO THE
 TRANSFORMER.
  
 3} INDICATE THE NUMBER OF CONDUCTORS FROM THE PANEL TO
 THE AIR HANDLER DISCONNECT AND IF GROUNDED.215.5 NEC.
  
 4} INDICATE THE NUMBER OF CONDUCTORS FROM THE PANEL TO
 THE CONDENSER DISCONNECT AND IF GROUNDED.215.5 NEC.
  
 5} THE LPD PER SQUARE FT IS SHOWN AS 2.1. THE CORRECT
 LPD FOR RETAIL IS 1.5 PER13-415.2.C.1 FBC. THE ALLOWED
 DENSITIES ARE COMPLIANT, THE CALCULATION SHOULD
 INDICATE 1.5 W/SQFT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  