| Date |
Text |
| 2009-01-22 16:30:56 | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 08070709 |
| | ADD: 480 HIBISCUS ST. #104 |
| | CONT: THE TOWER GROUP |
| | TEL: (954)476-3200 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1-22-09 |
| | REVIEW: 3RD |
| | ACTION: DENIED |
| | |
| | 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) OK |
| | |
| | **IS THIS A MERCANTILE OCCUPANCY ONLY; IF BUSINESS |
| | OFFICES ARE LOCATED IN THIS SPACE THEN, THE OCCUPANCY |
| | MAY CHANGE. CLARIFY. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICENT CLARITY. 106.1.1** |
| | 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE |
| | 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO |
| | BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE |
| | LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4. |
| | PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION |
| | FOR THE UNIFORM AND CONCENTRATED LOAD. **NOTE THE |
| | SPIRAL STAIRS SHALL MEET THE REQUIREMENTS OF FBC |
| | 1009.9.2. SO PLEASE INDICATE THE OCCUPANT LOAD OF THE |
| | MEZZANINE. THE PLANS NEED TO CLEARLY STATE THE USE OF |
| | THE MEZZANINE. THE MEZZANINE SPACE CANNOT BE INCLUDED |
| | WHEN CALCULATING THE OCCUPANT LOAD. |
| | |
| | **NO RESPONSE NOT ADDRESSED** |
| | 4) FBC 505.1 MEZZANINES ARE REQUIRED TO HAVE A CEILING |
| | HEIGHT OF NOT LESS THAN 7 FEET AND THE CEILING BELOW |
| | MUST ALSO BE AT LEAST 7 FEET. PROVIDE A FRONT ELEVATION |
| | OF THE MEZZANINE SHOWING THESE REQUIREMENTS. |
| | |
| | 5) OK |
| | 6) OK |
| | 7) OK |
| | 8) OK |
| | |
| | **THE BUILDING OFFICIAL MAY ESTABLISH THROUGH |
| | DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND |
| | SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS |
| | RECORD RETENTION PROGRAM. HANDWRITING AND WHITE-OUT ON |
| | THE PLANS IS NOT ACCEPTABLE. THE ARCHITECT IS NOT AWARE |
| | OF THE INFORMATION WRITTEN ON THE DRAWINGS. THE REVIEW |
| | STAMP IS SUFFICIENT INFORMATION. THE HANDWRITING |
| | INFORMATION NEEDS TO BE REMOVED FROM THE DRAWINGS. |
| | PLEASE SEE EACH SHEET. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | PHONE (561) 805-6726 |
| | FAX (561)805-6676 |
| | [email protected] |
| | |