| 2008-11-15 16:32:02 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1. THIS APPLICATION IS FOR A TENANT IMPROVEMENT IN A |
| | BUILDING WHICH IS NOT YET COMPLETED. IF THIS PERMIT IS |
| | TO BE ISSUED PRIOR TO C.O. OF THE BASE BUILDING, THE |
| | DESIGNERS F THE BASE BUILDING SHALL PERFORM A SHOP |
| | DRAWING REVIEW OF THESE PLANS AND APPROVE THEM IN |
| | WRITING (SHOP DRAWING REVIEW STAMP). THIS IS TO ENSURE |
| | THAT THE BASE BUILDING DESIGNERS ARE AWARE OF ANY |
| | CHANGES WHICH MAY BE MADE THAT WILL ALTER THE BASE |
| | BUILDING DESIGN OR PLANS PRIOR TO FINAL INSPECTIONS. IN |
| | ADDITION, ANY NEW INFORMATION PROVIDED REGARDING ENERGY |
| | UTILIZING SYSTEMS IN THIS SPACE WILL NEED TO BE |
| | INCLUDED IN THE BASE BUILDING ENERGY CALCULATIONS AND |
| | SUBMITTED AS A REVISION PRIOR TO C.O. OF THE BASE |
| | BUILDING. |
| | |
| | 2. OK |
| | |
| | 3. **PARTIALLY ADDRESSED** PAGE M1 DUCT TAKEOFF DETAIL: |
| | IN NO CASE SHALL THE MATERIAL SUPPORTING FLEXIBLE DUCT |
| | THAT IS IN DIRECT CONTACT WITH IT BE LESS THAN 1.5 |
| | INCHES WIDE IN ACCORDANCE WITH FBCM 603.5.6.6. |
| | |
| | 4. OK |
| | |
| | 5. OK |
| | |
| | 6. **NOT ADDRESSED** PAGE M1 PLUMBING NOTE #18: THIS |
| | NOTE CALLS FOR PVC O BE USED FOR THE CONDENSATE DRAIN |
| | LINE. PVC MAY NOT BE USED IN THE MECHANICAL ROOM WHICH |
| | ALSO SERVES AS A RETURN AIR PLENUM. MATERIALS EXPOSED |
| | WITHIN PLENUMS SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A |
| | FLAME SPREAD INDEX OF NOT MORE THAN 25 AND A |
| | SMOKE-DEVELOPED INDEX OF NOT MORE THAN 50 WHEN TESTED |
| | IN ACCORDANCE WITH ASTM E 84 PER FBCM 602.2.1. |
| | |
| | 7. OK |
| | |
| | 8. **NOT ADDRESSED** NO INFORMATION COULD BE FOUND |
| | REGARDING THE TYPE OF DOOR TO BE USED ON MECHANICAL |
| | ROOM 104. IS THIS DOOR WOOD OR OF NON-COMBUSTIBLE |
| | MATERIAL? SEE COMMENT #6 ABOVE FOR THE REQUIREMENTS FOR |
| | MATERIALS EXPOSED IN PLENUMS. PROVIDE THE MISSING |
| | INFORMATION ON THE PLANS. |
| | |
| | 9. SEE ABOVE. |
| | |
| | 10. OK |
| | |
| | 11. OK |
| | |