| 2008-11-19 10:42:31 | BUILDING PLAN REVIEW |
| | PERMIT: 08070709 |
| | ADD: 480 HIBISCUS ST. #104 |
| | CONT: THE TOWER GROUP |
| | TEL: (954)476-3200 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 11-19-08 |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | 1) OK |
| | |
| | 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF |
| | COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST |
| | INSPECTION. |
| | |
| | **IS THIS A MERCANTILE OCCUPANCY ONLY; IF BUSINESS |
| | OFFICES ARE LOCATED IN THIS SPACE THEN, THE OCCUPANCY |
| | MAY CHANGE. CLARIFY. CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICENT CLARITY. 106.1.1** |
| | 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE |
| | 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO |
| | BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE |
| | LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4. |
| | PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION |
| | FOR THE UNIFORM AND CONCENTRATED LOAD. **NOTE THE |
| | SPIRAL STAIRS SHALL MEET THE REQUIREMENTS OF FBC |
| | 1009.9.2. SO PLEASE INDICATE THE OCCUPANT LOAD OF THE |
| | MEZZANINE. THE PLANS NEED TO CLEARLY STATE THE USE OF |
| | THE MEZZANINE. THE MEZZANINE SPACE CANNOT BE INCLUDED |
| | WHEN CALCULATING THE OCCUPANT LOAD. |
| | |
| | **NO RESPONSE NOT ADDRESSED** |
| | 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE |
| | A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT |
| | BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING |
| | SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE |
| | DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET. |
| | THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE |
| | BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481. |
| | |
| | **AFTER FURTHER INVESTIGATION, I FOUND OUT THIS IS A |
| | NEW BUILDING THAT HAS NOT BEING OCCUPIED. THEREFORE, NO |
| | ALTERATION LEVEL IS REQUIRED.** |
| | 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS |
| | THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE |
| | AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A |
| | TWELVE MONTH PERIOD; BECAUSE THE SPACE HAS NEVER BEEN |
| | OCCUPIED, THIS WILL BE CONSIDERED AS NEW CONSTRUCTION |
| | SO, NO ALTERATION LEVEL IS REQUIRED. |
| | |
| | 6) OK |
| | 7) OK |
| | |
| | **NO VERTICAL ACCESSIBILITY SHALL BE PROVIDED IF THE |
| | REQUIREMENTS ARE MET** |
| | 8) 11-4.1.3(5) (3) OCCUPIABLE SPACES AND ROOMS THAT ARE |
| | NOT OPEN TO THE PUBLIC AND THAT HOUSE NO MORE THAN FIVE |
| | PERSONS INCLUDING, BUT NOT LIMITED TO, EQUIPMENT |
| | CONTROL ROOMS AND PROJECTION BOOTHS. HOWEVER AS |
| | PROVIDED IN SECTION 553.509, FLORIDA STATUTES, |
| | BUILDINGS, STRUCTURES, AND FACILITIES MUST, AT A |
| | MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADAAG. |
| | THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY BE |
| | REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS OTHERWISE |
| | EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS CODE. SHEET |
| | A.1 INDICATES WHAT APPEARS TO BE A CONFERENCE ROOM AT |
| | THE MEZZANINE LEVEL WITH MORE THAN FIVE PERSONS, WHICH |
| | WILL REQUIRE VERTICAL ACCESSIBILITY . |
| | |
| | NOTE: PLEASE INDICATE THE TYPE AND MAKE OF THE |
| | MECHANICAL ROOM DOOR. IS THE DOOR A NON-COMBUSTIBLE |
| | DOOR? ADDITIONAL INFORMATION IS REQUIRED 106.1.2. |
| | |
| | A) A FINISH SCHEDULE WAS NOT PROVIDED FOR THE ROOMS OR |
| | DOORS. FBC 1210.02 WALLS WITHIN 2 FEET OF URINALS AND |
| | WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT |
| | SURFACE TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. SHOW |
| | COMPLIANCE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |