Plan Review Notes
Plan Review Notes For Permit 08070709
Permit Number 08070709
Review Stop B
Sequence Number 2
Notes
Date Text
2008-11-19 10:42:31BUILDING PLAN REVIEW
 PERMIT: 08070709
 ADD: 480 HIBISCUS ST. #104
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 11-19-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) OK
  
 2) NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 **IS THIS A MERCANTILE OCCUPANCY ONLY; IF BUSINESS
 OFFICES ARE LOCATED IN THIS SPACE THEN, THE OCCUPANCY
 MAY CHANGE. CLARIFY. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICENT CLARITY. 106.1.1**
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD. **NOTE THE
 SPIRAL STAIRS SHALL MEET THE REQUIREMENTS OF FBC
 1009.9.2. SO PLEASE INDICATE THE OCCUPANT LOAD OF THE
 MEZZANINE. THE PLANS NEED TO CLEARLY STATE THE USE OF
 THE MEZZANINE. THE MEZZANINE SPACE CANNOT BE INCLUDED
 WHEN CALCULATING THE OCCUPANT LOAD.
  
 **NO RESPONSE NOT ADDRESSED**
 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT
 BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING
 SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE
 DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET.
 THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE
 BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481.
  
 **AFTER FURTHER INVESTIGATION, I FOUND OUT THIS IS A
 NEW BUILDING THAT HAS NOT BEING OCCUPIED. THEREFORE, NO
 ALTERATION LEVEL IS REQUIRED.**
 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS
 THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE
 AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A
 TWELVE MONTH PERIOD; BECAUSE THE SPACE HAS NEVER BEEN
 OCCUPIED, THIS WILL BE CONSIDERED AS NEW CONSTRUCTION
 SO, NO ALTERATION LEVEL IS REQUIRED.
  
 6) OK
 7) OK
  
 **NO VERTICAL ACCESSIBILITY SHALL BE PROVIDED IF THE
 REQUIREMENTS ARE MET**
 8) 11-4.1.3(5) (3) OCCUPIABLE SPACES AND ROOMS THAT ARE
 NOT OPEN TO THE PUBLIC AND THAT HOUSE NO MORE THAN FIVE
 PERSONS INCLUDING, BUT NOT LIMITED TO, EQUIPMENT
 CONTROL ROOMS AND PROJECTION BOOTHS. HOWEVER AS
 PROVIDED IN SECTION 553.509, FLORIDA STATUTES,
 BUILDINGS, STRUCTURES, AND FACILITIES MUST, AT A
 MINIMUM, COMPLY WITH THE REQUIREMENTS OF THE ADAAG.
 THEREFORE, FACILITIES SUBJECT TO THE ADAAG MAY BE
 REQUIRED TO PROVIDE VERTICAL ACCESS TO AREAS OTHERWISE
 EXEMPT UNDER SECTION 11-4.1.3 (5) OF THIS CODE. SHEET
 A.1 INDICATES WHAT APPEARS TO BE A CONFERENCE ROOM AT
 THE MEZZANINE LEVEL WITH MORE THAN FIVE PERSONS, WHICH
 WILL REQUIRE VERTICAL ACCESSIBILITY .
  
 NOTE: PLEASE INDICATE THE TYPE AND MAKE OF THE
 MECHANICAL ROOM DOOR. IS THE DOOR A NON-COMBUSTIBLE
 DOOR? ADDITIONAL INFORMATION IS REQUIRED 106.1.2.
  
 A) A FINISH SCHEDULE WAS NOT PROVIDED FOR THE ROOMS OR
 DOORS. FBC 1210.02 WALLS WITHIN 2 FEET OF URINALS AND
 WATER CLOSETS SHALL HAVE A SMOOTH, HARD, NONABSORBENT
 SURFACE TO A HEIGHT OF 4 FEET ABOVE THE FLOOR. SHOW
 COMPLIANCE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]