2009-01-22 15:26:46BUILDING PLAN REVIEW
 PERMIT: 08070708
 ADD: 480 HIBISCUS ST. #105
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1-22-09
 REVIEW: 3RD
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) OK
  
 **IS THIS A MERCANTILE OCCUPANCY ONLY; IF BUSINESS
 OFFICES ARE LOCATED IN THIS SPACE THEN, THE OCCUPANCY
 MAY CHANGE. CLARIFY. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICENT CLARITY. 106.1.1**
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD. **NOTE THE
 SPIRAL STAIRS SHALL MEET THE REQUIREMENTS OF FBC
 1009.9.2. SO PLEASE INDICATE THE OCCUPANT LOAD OF THE
 MEZZANINE. THE PLANS NEED TO CLEARLY STATE THE USE OF
 THE MEZZANINE. THE MEZZANINE SPACE CANNOT BE INCLUDED
 WHEN CALCULATING THE OCCUPANT LOAD.
  
 **NO RESPONSE NOT ADDRESSED**
 4) FBC 505.1 MEZZANINES ARE REQUIRED TO HAVE A CEILING
 HEIGHT OF NOT LESS THAN 7 FEET AND THE CEILING BELOW
 MUST ALSO BE AT LEAST 7 FEET. PROVIDE A FRONT ELEVATION
 OF THE MEZZANINE SHOWING THESE REQUIREMENTS.
  
 5) OK
 6) OK
 7) OK
  
 **THE BUILDING OFFICIAL MAY ESTABLISH THROUGH
 DEPARTMENTAL POLICY, STANDARDS FOR PLANS AND
 SPECIFICATIONS, IN ORDER TO PROVIDE CONFORMITY TO ITS
 RECORD RETENTION PROGRAM. HANDWRITING AND WHITE-OUT ON
 THE PLANS IS NOT ACCEPTABLE. THE ARCHITECT IS NOT AWARE
 OF THE INFORMATION WRITTEN ON THE DRAWINGS. THE REVIEW
 STAMP IS SUFFICIENT INFORMATION. THE HANDWRITING
 INFORMATION NEEDS TO BE REMOVED FROM THE DRAWINGS.
 PLEASE SEE EACH SHEET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 PHONE (561) 805-6726
 FAX (561)805-6676
 [email protected]
  