Plan Review Notes
Plan Review Notes For Permit 08070708
Permit Number 08070708
Review Stop E
Sequence Number 2
Notes
Date Text
2008-11-17 11:16:58 
  
  
 ** FAILED 2ND REVIEW **
  
  
 1) NOTE: SAME NOTE AS ON PREVIOUS REVIEW:
 THE BASE BUILDING DOES NOT HAVE A CERTIFICATE OF
 OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT PERMITTED
 BEFORE THE C OF O OF BASE BUILDING ARE TO CONTAIN A
 *SHOP DRAWING* REVIEW STAMP AND SIGNATURE FROM THE BASE
 BUILDING DESIGNERS OF RECORD ON EACH RELEVANT SHEET.
 THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL SUCH TIME A C OF O IS ISSUED.
 FS 471,481
  
 2) NOTE: SAME NOTE AS ON PREVIOUS REVIEW:
 PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR BUILD OUT
 BEFORE THE C OF O IS ISSUED ON BASE BUILDING WILL
 REQUIRE THE FOLLOWING TO BE REVISED.
 THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE
 REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS.
 220
 THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED
 FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS
 TO NEW KNOWN ENERGY USE.
 THIS INCLUDES ALL NEW LIGHTING.
 FBC CHAPTER 13.
  
 3) NOTE: SAME AS PREVIOUS REVIEW:
 THE PLANS STILL INDICATE EXISTING RETAIL HOWEVER THIS
 IS NOT POSSIBLE AS THE BUILDING CONTAINS *SHELL* SPACES
 FOR FUTURE. THE PLANS NEED TO BE ADJUSTED ACCORDINGLY.
 FBC 301.1
 FBC 106.1.1,106.5 FOR CLARITY, COORDINATION OF RECORD
 PLANS.
  
 4) NOTE: SAME AS PREVIOUS REVIEW:
 PLEASE SEE THE SUBMITTED LIGHTING AND LIGHTING
 CALCULATIONS FOR PERFORMANCE LEVELS STILL NEED TO BE
 ADDRESSED AND DESIGNED FOR CODE COMPLIANCE. THE
 LIGHTING SHOWN ON SHEET A.2 IS DIFFERENT FROM THE
 LIGHTING SHOWN ON ELECTRICAL PLANS. THE LENGTH OF TRACK
 THE NUMBER OF TRACK FIXTURES ETC.
 PLEASE SEE THAT THE LIGHTING ON PLAN NEED TO BE
 IDENTIFIED WITH SOME SORT OF DESIGNATION SO LIGHTING
 DESIGN WATTAGE CANE BE REVIEWED AND CONFIRMED. PLEASE
 BE SURE TO SEE THE SECTIONS OF THE CODE BELOW WITH
 INFORMATION AND DESIGN FOR TRACK LIGHTING.
  
 PLEASE COORDINATE ALL ITEMS.
 **NOT ALL AREAS ARE RETAIL.
  
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS IN
 COMPLIANCE WITH FBC 13-415.2, 13-415.2.ABC.1.1, .1.2.
 13-415.2.B
  
 5) NOTE: THE RISER INDICATES A DISCONNECT AND
 TRANSFORMER WHICH WOULD BE LOCATED IN THE STORAGE
 CLOSET ON MEZZANINE LEVEL WHICH IS NOT PERMITTED.
 THE ELECTRICAL PLANS DO NOT SHOW EITHER OF THESE TWO ON
 MEZZANINE LEVEL AND ONLY SHOWS THE PANEL.
 PLEASE SHOW LOCATIONS OF ALL EQUIPMENT, LABEL
 ACCORDINGLY TO RISER AND PANEL IDENTIFICATION.
 PLEASE SEE 240.21,450.9,450.13,450.21, 240.24 ETC
 THIS AS SHOWN ON PLANS IS CLEARLY A STORAGE CLOSET
 WHICH WILL CONTAIN COMBUSTIBLES AND EASILY IGNITABLE
 MATERIALS. THIS IS A FIRE AND LIFE SAFETY HAZARD.
 PLEASE ADJUST, RE-LOCATE ETC.
  
 6) NOTE: FROM PREVIOUS REVIEW:
 PLEASE INCLUDE THE DEVICE LOCATIONS, LEVELS, AND
 HEIGHTS FOR ALL FIRE ALARM DEVICES FOR ADA COMPLIANCE.
 FBC 11-4.28.1,.2 AND .3.
  
 7) NOTE: PLEASE SEE THE PANEL SCHEDULE NEEDS TO BE
 SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. USING
 *RECEPTACLES* OR *LIGHTING* IS NOT SPECIFIC. PLEASE SEE
 THE 2005 NEC CHANGE IN THE HANDBOOK UNDER 408.4 AS THIS
 WAS SPECIFICALLY REVISED.
  
 8) NOTE: PLEASE SEE NOTICE TOT FS 553.80(2)(B) IS GIVEN
 AT THIS TIME DUE TO SOME COMMENTS BEING REPEATED . THIS
 ONLY A NOTICE GIVEN AT THIS TIME.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  