2008-08-08 15:25:56PLUMBING PLAN REVIEW:
 DENIED:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A.3 KEY NOTES #8, #9 AND SHEET M1 PLUMBING
 FIXTURE SCHEDULE MARK 1, 2 ARE INDICATING DIFFERENT
 MODEL FIXTURES FOR THE WATER CLOSET, LAVATORIES AND THE
 LAVATORY FAUCETS. PLEASE KNOW THAT AN ONLINE SEARCH FOR
 THE INDICATED AMERICAN STANDARD FIXTURE MODELS CAME UP
 "NO RECORDS TO DISPLAY FOR THOSE FIXTURES. PLEASE
 CORRECT, CORRELATE, AND PROVIDE MANUFACTURER SPEC
 SHEETS FOR FIXTURES. PER FBC-2004 PLUMBING SECTION
 401.1 SCOPE.
  
 2. SHEET M1 SANITARY ISOMETRIC: PLEASE CORRECT THE
 FOLLOWING PER THE FBC-2004 PLUMBING SECTIONS.
  
 A} CLEARLY INDICATE THE SIZE OF THE LAVATORY AND
 DRINKING FOUNTAIN WATER-SEAL TRAPS. PLEASE KNOW THAT IF
 TRAPS ARE 1-1/4"CLEANOUTS WILL BE REQUIRED AT THE
 BASE OF THEIR STACKS. PER SECTION 701.1 SCOPE AND
 SECTION 708.3.4. BASE OF STACK.
  
 3. SHEET M1 HVAC & PLUMBING: CLEARLY INDICATE ON THE
 RESUBMITTED PLANS WHERE THE CONDENSATE TIE-IN DRAIN
 PIPING TERMINATION POINT IS. DOES IT TIE INTO AN
 EXISTING SYSTEM? PLEASE KNOW THAT THE CONDENSATE SHALL
 NOT DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS SO AS
 TO CAUSE A NUISANCE. PER SECTION 314.2.1 CONDENSATE
 DISPOSAL.
  
 4. THE PROPOSED BUILD-OUT OF SUITE 106 IS IN A BASE
 BUILDING THAT DOES NOT YET HAVE A CERTIFICATE OF
 OCCUPANCY, SO THE BASE BUILDING DESIGN PROFESSIONALS
 WILL BE REQUIRED TO PROVIDE A SHOP DRAWING REVIEW STAMP
 ON ANY BUILD-OUT PLANS THAT ARE PREPARED BY DIFFERENT
 DESIGNERS. PER FS 481, 481.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  