Plan Review Notes
Plan Review Notes For Permit 08070708
Permit Number 08070708
Review Stop E
Sequence Number 1
Notes
Date Text
2008-08-08 09:19:27 
 **DENIEDREVIEW**
  
  
  
 1) NOTE:THE BASE BUILDING DOES NOT HAVE A CERTIFICATE
 OF OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT
 PERMITTED BEFORE THE C OF O OF BASE BUILDING ARE TO
 CONTAIN A *SHOP DRAWING* REVIEW STAMP AND SIGNATURE
 FROM THE BASE BUILDING DESIGNERS OF RECORD ON EACH
 RELEVANT SHEET.
 THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE
 BUILDING UNTIL SUCH TIME A C OF O IS ISSUED.
 FS 471,481
  
 2) NOTE: PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR
 BUILD OUT BEFORE THE C OF O IS ISSUED ON BASE BUILDING
 WILL REQUIRE THE FOLLOWING TO BE REVISED.
 THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE
 REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS.
 220
 THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED
 FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS
 TO NEW KNOWN ENERGY USE.
 THIS INCLUDES ALL NEW LIGHTING.
 FBC CHAPTER 13.
  
 3) NOTE: PLEASE SUBMIT AND SHOW THE LIGHTING LEVELS IN
 PHOTO-METRICS ON STAIRS PER NFPA-101 2003, 7.8.1.3,
 7.9.2.1, .2.2.
  
 4) NOTE: PLEASE INDICATE ALL LIGHTING CONTROLS REQUIRED
 PER FBC 13-415.1.ABC.1.1,.1.2 AND .1.3.
 THE SYMBOL LEGEND DOES INDICATE SOME OCCUPANCY SENSOR
 TYPE DEVICES HOWEVER NONE OF THIS DEVICE S IS ON PLANS.
 IN FACT THE PLANS ONLY INDICATE STANDARD SWITCHING
 DEVICES WHICH ARE NOT PERMITTED.
 PLEASE PROVIDE ALL MAXIMUM TIMES ON ALL DEVICES.
 PLEASE BE SURE TO SEE NFPA-101 7.8.1.2.2 AND FBC
 1006.1.2 AS ANY OCCUPANCY SENSOR FOR ANY EGRESS
 LIGHTING SHALL BE * FAIL SAFE ON*.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS IN COMPLIANCE WITH FBC 13-415.2,
 13-415.2.ABC.1.1, .1.2.
 PLEASE SUBMIT THE FIXTURE SCHEDULE/LEGEND.
 PLEASE SEE THE SECTIONS OF THE CODE ABOVE. THE WATTAGE
 TO BE USED IS BASED ON THE FIXTURE WATTAGE NOT THE LAMP
 WATTAGE AS STATED ON PLANS.
 PLEASE KNOW AS THE PLANS ARE NOT COMPLETE WITH A
 FIXTURE LEGEND ETC SOME OF THESE ITEMS FOR CODE
 COMPLIANCE CAN NOT BE DETERMINED AT THIS TIME.
  
 6) NOTE: PLEASE PROVIDE VOLTAGE DROP PER
 13-413.1.ABC.1.2 FOR CU.
  
 7) NOTE: PLEASE COMPLETE PANEL SCHEDULE FOR ALL
 CIRCUITS TO SPECIFIC AREAS AND LOCATIONS.
 408.4
  
 8) NOTE:
  
 9) NOTE: PLEASE VERIFY RISER AS THE GUTTER IS INDICATED
 AS RAIN TIGHT? PLEASE ALSO INDICATE THE SIZE/AMPERAGE
 OF THE GUTTER PROVIDED.
 PLEASE INDICATE A FLOATING NEUTRAL ON THE NEW METER AS
 THE MAIN FOR TENANT SHOWN WILL BE AFTER A MEANS OF
 DISCONNECT FOR SERVICE.
 250.24, 250.6
  
 10) NOTE: PLEASE SEE 600.5 AS THE LOAD FOR A SIGN
 CIRCUIT IS REQUIRED TO BE FIGURED AT 1200VA. THIS WOULD
 BE 10AMPS ON THE CIRCUIT.
  
 11) NOTE: PLEASE SEE 210.62 FOR MISSING SHOW WINDOW
 RECEPTACLES.
 PLEASE ALSO SEE 220.43
  
 12) NOTE: PLEASE INCLUDE LOADS FOR TRACK LIGHTING PER
 220.43
  
 13) NOTE: BASE BUILD OUT PLANS SHALL INCLUDE DEVICES TO
 COMPLY WITH THE FIRE CODES, SUCH AS NFPA-1, NFPA-72 AND
 FBC 2004 W/2007 REVISIONS.
 PLEASE SEE FBC 11-4.28 (ALL) AND INDICATE REQUIRED
 DEVICES ACCORDINGLY
  
 ** PLEASE KNOW AS THERE ARE SOME ITEMS NOT YET ON
 DESIGN SHEETS THERE MAY VERY WELL BE NEW COMMENTS ON
 THE FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS
 TIME.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]