2008-08-15 16:33:42BUILDING PLAN REVIEW
 PERMIT: 08070708
 ADD: 480 HIBISCUS ST. #105
 CONT: THE TOWER GROUP
 TEL: (954)476-3200
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 8-15-08
 REVIEW: 1ST
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT. NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) INDICATE THE OCCUPANT LOAD OF THE SPACE PER TABLE
 1004.1.2. THE OCCUPANT LOAD OF THE MEZZANINE SHALL ALSO
 BE INDICATED; STATE THE USE OF THE MEZZANINE AND THE
 LIVE LOAD OF THE FLOOR PER FBC 1603.3 AND 1603.4.
 PLEASE SEE TABLE 1607.1 FOR ADDITIONAL LOAD INFORMATION
 FOR THE UNIFORM AND CONCENTRATED LOAD.
  
 4) DUE TO THE FACT THAT THE BASE BUILDING DOES NOT HAVE
 A CERTIFICATE OF OCCUPANCY, ALL PROJECTS FOR TENANT
 BUILD OUT PERMITTED BEFORE THE CO OF THE BASE BUILDING
 SHALL HAVE A REVIEW STAMP AND THE SIGNATURE FROM THE
 DESIGNER OF RECORD OF THE BASE BUILDING ON EACH SHEET.
 THE BASE BUILDING DESIGNERS IS RESPONSIBLE FOR THE
 BUILDING UNTIL IT IS CO. FLORIDA STATUTES 471 AND 481.
  
 5) THE DRAWING INDICATES ALTERATION LEVEL 3 WHICH MEANS
 THE WORK IN THE AREA EXCEEDS 50 PERCENT OF THE
 AGGREGATE AREA OF THE BUILDING AND IS MADE WITHIN A
 TWELVE MONTH PERIOD; FBC(EXISTING) 305.1. IS THIS THE
 CASE FOR THIS PROJECT? IF NOT PLEASE SEE SECTION 304 OF
 THE FBC (EXISTING) ALTERATION LEVEL 2.
  
 7) FBC 1013.3 (EXCEPTION #5) SHOW THE COMMON PATH OF
 EGRESS TRAVEL WHICH SHALL BE 100 FEET IN BUILDINGS WITH
 AN AUTOMATIC SPRINKLER SYSTEM INSTALLED THROUGHOUT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]