| 2008-11-17 10:34:31 | |
| | |
| | |
| | ** FAILED 2ND REVIEW ** |
| | |
| | |
| | 1) NOTE: SAME NOTE AS ON PREVIOUS REVIEW: |
| | THE BASE BUILDING DOES NOT HAVE A CERTIFICATE OF |
| | OCCUPANCY. ALL PROJECTS FOR TENANT BUILD OUT PERMITTED |
| | BEFORE THE C OF O OF BASE BUILDING ARE TO CONTAIN A |
| | *SHOP DRAWING* REVIEW STAMP AND SIGNATURE FROM THE BASE |
| | BUILDING DESIGNERS OF RECORD ON EACH RELEVANT SHEET. |
| | THE BASE BUILDING DESIGN TEAM IS RESPONSIBLE FOR THE |
| | BUILDING UNTIL SUCH TIME A C OF O IS ISSUED. |
| | FS 471,481 |
| | |
| | 2) NOTE: SAME NOTE AS ON PREVIOUS REVIEW: |
| | PLEASE KNOW THAT ANY PERMITTED PROJECTS FOR BUILD OUT |
| | BEFORE THE C OF O IS ISSUED ON BASE BUILDING WILL |
| | REQUIRE THE FOLLOWING TO BE REVISED. |
| | THE BASE BUILDING LOAD CALCULATIONS ARE REQUIRED TO BE |
| | REVISED TO INDICATE AND SHOW ALL NEW KNOWN LOADS. |
| | 220 |
| | THE BASE BUILDING ENERGY CALCULATIONS SHALL BE REVISED |
| | FROM WHAT WAS ENTERED AS *ASSUMPTIONS* ON CALCULATIONS |
| | TO NEW KNOWN ENERGY USE. |
| | THIS INCLUDES ALL NEW LIGHTING. |
| | FBC CHAPTER 13. |
| | |
| | 3) NOTE: SAME AS PREVIOUS REVIEW: |
| | THE PLANS STILL INDICATE EXISTING RETAIL HOWEVER THIS |
| | IS NOT POSSIBLE AS THE BUILDING CONTAINS *SHELL* SPACES |
| | FOR FUTURE. THE PLANS NEED TO BE ADJUSTED ACCORDINGLY. |
| | FBC 301.1 |
| | FBC 106.1.1,106.5 FOR CLARITY, COORDINATION OF RECORD |
| | PLANS. |
| | |
| | 4) NOTE: SAME AS PREVIOUS REVIEW: |
| | PLEASE SEE THE SUBMITTED LIGHTING AND LIGHTING |
| | CALCULATIONS FOR PERFORMANCE LEVELS STILL NEED TO BE |
| | ADDRESSED AND DESIGNED FOR CODE COMPLIANCE.. THE |
| | LIGHTING SHOWN ON SHEET A.2 IS DIFFERENT FROM THE |
| | LIGHTING SHOWN ON ELECTRICAL PLANS. IN FACT THERE ARE |
| | DIFFERENT FIXTURES, DIFFERENT WATTAGES ETC. PLEASE ALSO |
| | SEE THE LIGHTING SHOWN ON E-1 AND E-2 ARE NOT THE SAME. |
| | THE LENGTH OF TRACK THE NUMBER OF TRACK FIXTURES ETC. |
| | PLEASE SEE ELECTRICAL PLANS AS THERE IS NO FIXTURE |
| | SCHEDULE AND IDENTIFICATION A COMPLETE REVIEW COULD NOT |
| | TO BE DONE. |
| | PLEASE COORDINATE ALL ITEMS. |
| | NOT ALL AREAS ARE RETAIL. |
| | |
| | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS IN |
| | COMPLIANCE WITH FBC 13-415.2, 13-415.2.ABC.1.1, .1.2. |
| | 13-415.2.B |
| | |
| | 5) NOTE: THE RISER INDICATES A DISCONNECT AND |
| | TRANSFORMER WHICH WOULD BE LOCATED IN THE STORAGE |
| | CLOSET ON MEZZANINE LEVEL WHICH IS NOT PERMITTED. |
| | THE ELECTRICAL PLANS DO NOT SHOW EITHER OF THESE TWO ON |
| | MEZZANINE LEVEL AND ONLY SHOWS THE PANEL. |
| | PLEASE SHOW LOCATIONS OF ALL EQUIPMENT, LABEL |
| | ACCORDINGLY TO RISER AND PANEL IDENTIFICATION. |
| | PLEASE SEE 240.21,450.9,450.13,450.21, 240.24 ETC |
| | THIS AS SHOWN ON PLANS IS CLEARLY A STORAGE CLOSET |
| | WHICH WILL CONTAIN COMBUSTIBLES AND EASILY IGNITABLE |
| | MATERIALS. THIS IS A FIRE AND LIFE SAFETY HAZARD. |
| | PLEASE ADJUST, RE-LOCATE ETC. |
| | |
| | 6) NOTE: FROM PREVIOUS REVIEW: |
| | PLEASE INCLUDE THE DEVICE LOCATIONS, LEVELS, AND |
| | HEIGHTS FOR ALL FIRE ALARM DEVICES FOR ADA COMPLIANCE. |
| | FBC 11-4.28.1,.2 AND .3. |
| | |
| | 7) NOTE: PLEASE SEE THE PANEL SCHEDULE NEEDS TO BE |
| | SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. USING |
| | *RECEPTACLES* OR *LIGHTING* IS NOT SPECIFIC. PLEASE SEE |
| | THE 2005 NEC CHANGE IN THE HANDBOOK UNDER 408.4 AS THIS |
| | WAS SPECIFICALLY REVISED. |
| | |
| | 8) NOTE: PLEASE SEE NOTICE TOT FS 553.80(2)(B) IS GIVEN |
| | AT THIS TIME DUE TO SOME COMMENTS BEING REPEATED . THIS |
| | ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |