Plan Review Notes
Plan Review Notes For Permit 08070706
Permit Number 08070706
Review Stop M
Sequence Number 1
Notes
Date Text
2008-08-18 16:47:33REVIEW #: 1ST
 ACTION: DENIED
  
 REVIEWED UNDER THE FOLLOWING CODES:
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. THIS APPLICATION IS FOR A TENANT IMPROVEMENT IN A
 BUILDING WHICH IS NOT YET COMPLETED. IF THIS PERMIT IS
 TO BE ISSUED PRIOR TO C.O. OF THE BASE BUILDING, THE
 DESIGNERS F THE BASE BUILDING SHALL PERFORM A SHOP
 DRAWING REVIEW OF THESE PLANS AND APPROVE THEM IN
 WRITING (SHOP DRAWING REVIEW STAMP). THIS IS TO ENSURE
 THAT THE BASE BUILDING DESIGNERS ARE AWARE OF ANY
 CHANGES WHICH MAY BE MADE THAT WILL ALTER THE BASE
 BUILDING DESIGN OR PLANS PRIOR TO FINAL INSPECTIONS. IN
 ADDITION, ANY NEW INFORMATION PROVIDED REGARDING ENERGY
 UTILIZING SYSTEMS IN THIS SPACE WILL NEED TO BE
 INCLUDED IN THE BASE BUILDING ENERGY CALCULATIONS AND
 SUBMITTED AS A REVISION PRIOR TO C.O. OF THE BASE
 BUILDING.
  
 2. PROVIDE COOLING LOAD CALCULATIONS FOR THIS SPACE IN
 ACCORDANCE WITH FBCB 13-407.1.ABC.1.
  
 3. PAGE M1 DUCT TAKEOFF DETAIL: HORIZONTAL DUCT SHALL
 BE SUPPORTED AT INTERVALS NOT GREATER THAN 5 FEET AND
 HANGERS, SADDLES AND OTHER SUPPORTS SHALL MEET THE DUCT
 MANUFACTURER?S RECOMMENDATIONS AND SHALL BE OF
 SUFFICIENT WIDTH TO PREVENT RESTRICTION OF THE INTERNAL
 DUCT DIAMETER. IN NO CASE SHALL THE MATERIAL SUPPORTING
 FLEXIBLE DUCT THAT IS IN DIRECT CONTACT WITH IT BE LESS
 THAN 1? INCHES WIDE IN ACCORDANCE WITH FBCM 603.5.6.6.
  
 4. LOCATION OF CONDENSATE DISPOSAL NOT SHOWN ON PLANS.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE IN ACCORDANCE WITH FBCM 307.2.1.
  
 5. PROVIDE AUXILIARY OR SECONDARY DRAIN PROTECTION IN
 ACCORDANCE WITH FBCM 307.2.3.
  
 6. PAGE M1 PLUMBING NOTE #18: THIS NOTE CALLS FOR PVC O
 BE USED FOR THE CONDENSATE DRAIN LINE. PVC MAY NOT BE
 USED IN THE MECHANICAL ROOM WHICH ALSO SERVES AS A
 RETURN AIR PLENUM. MATERIALS EXPOSED WITHIN PLENUMS
 SHALL BE NONCOMBUSTIBLE OR SHALL HAVE A FLAME SPREAD
 INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX
 OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM
 E 84 PER FBCM 602.2.1.
  
 7. PAGE M1: NO INFORMATION WAS PROVIDED ON PLANS
 REGARDING THE CFM OF THE TOILET ROOM EXHAUST FAN.
 PROVIDE A FAN SCHEDULE WITH MAKE, MODEL, VOLTS, AMPS
 AND EXHAUST RATE EXPRESSED IN CFM. EXHAUST RATE SHALL
 BE IN COMPLIANCE WITH FBCM 403.4 AND ASHRAE 62.1-2004
 TABLE 6-4.
  
 8. NO INFORMATION COULD BE FOUND REGARDING THE TYPE OF
 DOOR TO BE USED ON MECHANICAL ROOM 104. IS THIS DOOR
 WOOD OR OF NON-COMBUSTIBLE MATERIAL? SEE COMMENT #6
 ABOVE FOR THE REQUIREMENTS FOR MATERIALS EXPOSED IN
 PLENUMS. PROVIDE THE MISSING INFORMATION ON THE PLANS.
  
 9. MECHANICAL ROOM 104 IS SHOWN BEING USED AS A RETURN
 AIR PLENUM. NO INFORMATION COULD BE FOUND ON PLANS
 REGARDING HOW RETURN AIR IS TO FLOW INTO THE MECHANICAL
 ROOM. BALANCED RETURN AIR IS REQUIRED IN ACCORDANCE
 WITH FBCM 601.4. PLEASE SHOW ON MECHANICAL FLOOR PLANS
 HOW THIS IS TO BE ACHIEVED.
  
 10. THE OUTSIDE AIR INTAKE DUCT SHALL BE PROVIDED WITH
 AUTOMATIC SHUTOFF DAMPER CONTROLS IN ACCORDANCE WITH
 FBCB 13-409.1.ACB 3.3.
  
 11. THE OUTSIDE AIR CALCULATIONS DO NOT CORRESPOND WITH
 ASHRAE 62.1-2004 SECTION 6.2. EXAMPLE: THE OCCUPANCY
 SHOULD BE BASED ON A RETAIL OCCUPANCY ON TABLE 6-1.
 BASED ON THIS OCCUPANCY AND THE SIZE OF THE SPACE GIVEN
 ON THE PLANS, A MINIMUM VENTILATION RATE OF 227 CFM IS
 REQUIRED IN ACCORDANCE WITH FBCM 403.4 AND ASHRAE
 62.1-2004 SECTION 6.2.
  