| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC CHAPTER 1 |
| | AS AMENDED AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE DESCRIPTION ON THE APPLICATION DOES NOT INCLUDE |
| | A NEW BATHROOM.REVISE THE APPLICATION TO INCLUDE ALL |
| | WORK TO BE COMPLETED UNDER THIS PERMIT. 105.1 FBC. |
| | |
| | 2} 210.11(C)(1) SMALL-APPLIANCE BRANCH CIRCUITS IN |
| | ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY |
| | OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE |
| | SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR |
| | ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B)(1) |
| | RECEPTACLE OUTLETS SERVED IN THE KITCHEN, PANTRY, |
| | BREAKFAST ROOM, DINING ROOM, OR SIMILAR AREA OF A |
| | DWELLING UNIT, THE TWO OR MORE 20-AMPERE |
| | SMALL-APPLIANCE BRANCH CIRCUITS REQUIRED BY |
| | 210.11(C)(1) SHALL SERVE ALL WALL AND FLOOR RECEPTACLE |
| | OUTLETS COVERED BY 210.52(A), ALL COUNTERTOP OUTLETS |
| | COVERED BY 210.52(C), AND RECEPTACLE OUTLETS FOR |
| | REFRIGERATION EQUIPMENT.**ONLLY CIRCUIT 24, SHEET A-3 |
| | COMPLIES, CIRCUIT 26 HAS LIGHTS ON THE SAME CIRCUIT AS |
| | THE RECEPTACLES.CIRCUIT #2 IS NOT SHOWN IN THE |
| | KITCHEN. |
| | |
| | 3} NOTE #4 IN THE ELECTRICAL NOTES, SHEET A-3, |
| | REGARDING #12 COPPER CONDUCTORS MINIMUM IS IN CONFLICT |
| | WITH THE #14 WIRE ADDED IN CIRCUIT 28. |
| | |
| | 4} THE LOAD CALCULATION ONLY LISTS ONE SMALL APPLIANCE |
| | CIRCUIT, TWO ARE LISTED ON THE PANEL SCHEDULE AND ARE |
| | RQUIRED PER 210.11(C)(1). |
| | |
| | 5} R313.1.1 ALTERATIONS, REPAIRS AND ADDITIONS. |
| | WHEN INTERIOR ALTERATIONS, REPAIRS OR ADDITIONS |
| | REQUIRING A PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING |
| | ROOMS ARE ADDED OR CREATED IN EXISTING DWELLINGS, THE |
| | INDIVIDUAL DWELLING UNIT SHALL BE PROVIDED WITH SMOKE |
| | ALARMS LOCATED AS REQUIRED FOR NEW DWELLINGS; THE SMOKE |
| | ALARMS SHALL BE INTERCONNECTED AND HARD WIRED.*** |
| | INDICATE SAME ON PLANS, SHOW LOCATION OR NOTE THIS |
| | ARTICLE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |