| 2008-09-24 16:02:09 | ** DENIED 3RD REVIEW ** |
| | |
| | |
| | ** 2ND REVIEW UNDER PERMIT APPLICATION. |
| | |
| | |
| | 1) NOTE: LIGHTING PERFORMANCE CALCULATIONS NOW |
| | SUBMITTED FOR FIRST REVIEW ARE NOT CORRECT AND DO NOT |
| | MEET FBC 13-415.2,13-415.2.ABC.1.1, .1.2. |
| | PLEASE SEE IN FACT THE LIGHTING WATTAGES AS SHOWN FOR |
| | MOST ALL OF THE FIXTURES IS INDICATING EACH FIXTURE AS |
| | 35WATTS. HOW IS THIS POSSIBLE WHEN THE FIXTURE LEGEND |
| | CLEARLY INDICATES MANY OF THESE FIXTURES CONTAINING 3- |
| | T-8 BULBS? WHAT ARE THE WATTAGES OF THESE T-8 BULBS. |
| | BASED ON MOST MANUFACTURES ON THE MARKET, THIS OFFICE |
| | COULD NOT LOCATE ANY 11-13 WATT T-8 BULBS WHICH WOULD |
| | BE THE TOTAL AS SHOWN FOR EACH FIXTURE ON CALCULATIONS. |
| | PLEASE KNOW THAT EVEN WITH THE MOST EFFICIENT BALLAST |
| | ON THE MARKET KNOWN TO DATE, THE POWER FACTOR RATING |
| | WILL NOT TAKE 3-32WATT STANDARD T-* BULBS WHICH IS |
| | 96WATTS AND TAKE THE RATING DOWN TO 35WATTS FOR ALL |
| | THREE BULBS IN A SINGLE FIXTURE. AS SHOWN ON PLANS THE |
| | AMOUNT OF LIGHT EXCEEDS THE ALLOWANCES IN THE FLORIDA |
| | BUILDING CODE. |
| | THE WATTAGE WHICH IS REQUIRED TO BE USED IS THE FIXTURE |
| | WATTAGE NOT THE BULB WATTAGE. BASED ON PLANS AND |
| | INFORMATION AT THIS TIME THIS DOES NOT MEET THE FBC |
| | SECTIONS AS NOTED. |
| | ** PLEASE BE SURE TO COMPLETE THE FIXTURES ON LEGEND. |
| | AN EXAMPLE WOULD BE THE RESTROOM LIGHT WHICH IS NOT |
| | SPECIFIED. |
| | |
| | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. PLEASE KNOW ONE COPY OF |
| | ELECTRICAL PLANS/SHEETS HAVE BEEN RETAINED BY THIS |
| | OFFICE. |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |