| Plan Review Notes For Permit 08070695 |
| Permit Number |
08070695 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-09-10 10:37:15 | *** PROVISO *** | | | 1) BATHROOM EXHAUST FAN MUST COMPLY WITH 2004 FBC/M | | | 501.2 OUTDOOR DISCHARGE. THE AIR REMOVED BY EVERY | | | MECHANICAL EXHAUST SYSTEM SHALL BE DISCHARGED OUTDOORS | | | AT A POINT WHERE IT WILL NOT CAUSE A NUISANCE AND FROM | | | WHICH IT CANNOT AGAIN BE READILY DRAWN IN BY A | | | VENTILATING SYSTEM. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|