| Date |
Text |
| 2008-07-24 11:59:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | FOR PLAN REVIEW ONLY NOT FOR PERMIT. |
| | *** DENIED *** |
| | |
| | 1) PLAN PAGE A-0 STATES "NO MECHANICAL WORK PROPOSED" |
| | BUT PLAN PAGE E-1 LIGHTING PLAN SHOWS 6 NEW 12X12 |
| | RETURN AIR TRANSFER GRILLS WITH NO DUCTS. IS THE INTENT |
| | TO TURN THE ATTIC SPACE INTO A OPEN PLENUM? PLEASE |
| | SUBMIT MECHANICAL PLANS SHOWING ALL NEW AND ALTERED |
| | WORK, PER 2004 FBC 106.3.5. |
| | |
| | 2) PLAN E-1 SHOW A NEW BATHROOM EXHAUST FAN BEING |
| | INSTALLED, PLEASE SHOW ON MECHANICAL PLAN AND SHOW WERE |
| | IT WILL DISCHARGE TO, PER 2004 FBC/M 401.5.2. |
| | |
| | 3) PLAN E-1 ALSO SHOWS TWO NEW 24X48 RETURN AIR GRILLS |
| | AND ALL 24X24 SUPPLY AIR GRILLS BEING RELOCATED. PLEASE |
| | SHOW ON MECHANICAL PLAN WITH CFM'S AT ALL SUPPLY AIR |
| | GRILLS AND IF DUCT SIZES ARE BEING CHANGED SHOW NEW |
| | SIZE, PER 2004 FBC 106.3.5. |
| | |
| | 4) PLEASE SHOW ON MECHANICAL PLAN OUTDOOR AIR |
| | CALCULATIONS, PER 2004 FBC/M 403.2. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |