| 2008-08-11 14:52:42 | |
| | **DENIED** |
| | |
| | 1) NOTE: PLEASE KNOW PLANS ARE ONLY BEING SUBMITTED FOR |
| | PLAN REVIEW AND ARE NOT BEING SUBMITTED UNDER PERMIT |
| | APPLICATION. PLEASE KNOW EVEN ONCE PLANS ARE FOUND TO |
| | BE CODE COMPLIANT PLANS WILL REMAIN IN A FAILED STATUS |
| | UNTIL PERMIT IS APPLIED FOR. LICENSING OF DESIGNERS ETC |
| | WILL BE VERIFIED AFTER PERMIT APPLICATION. |
| | |
| | ** PLEASE ALSO VERIFY THAT THE PLANS WERE ALREADY |
| | SUBMITTED FOR *PLAN REVIEW * IN MARCH 08 UNDER TRACKING |
| | NUMBER 08030346. |
| | |
| | 2) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| | THE FOLLOWING MINIMUM CODES. |
| | 2004 FBC W/2007 REVISIONS |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (WHERE APPLICABLE) |
| | 2005 NFPA-70 |
| | |
| | ** STATING THE LATEST EDITION IS NOT PERMITTED. |
| | |
| | 2) NOTE: PLEASE KNOW BASED ON RISER AS SHOWN THE NEW |
| | SERVICE IS NOT PERMITTED OR FALL UNDER THE EXCEPTIONS |
| | OF 230.2 TO GRANT AN ADDITIONAL SERVICE. |
| | |
| | 3) NOTE: PLEASE SEE FBC 13-413.1.ABC.2.1 AND .2.2 AND |
| | PROVIDE NOTES ON PLANS ACCORDINGLY. |
| | |
| | 4) NOTE: PLEASE PROVIDE LIGHTING CONTROLS ARE REQUIRED |
| | PER 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE 13-415.1.ABC.1.4 FOR ANY OUTSIDE LIGHTING. |
| | SOME NOTES ON PLANS INDICATE SENSOR TYPE DEVICES OF |
| | SOME KIND HOWEVER NOT ENOUGH INFORMATION IS PROVIDED. |
| | NO TIMES ON DEVICES, DEVICES ARE NOT LISTED ON SYMBOL |
| | LEGEND, NO OTHER INFORMATION PROVIDED. ETC. |
| | |
| | 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE |
| | CALCULATIONS PER 13-415.2, 13-415.2.ABC.1.1 AND.1.2. |
| | MUST ALSO SUBMIT A COMPLETED FIXTURE LEGEND WITH ALL |
| | NEW FIXTURES. |
| | |
| | 6) NOTE: PLANS INDICATE CEILING MOUNTED OUTLET BOXES BY |
| | LANDLORD HOWEVER AS THIS IS A SEPARATE LEGAL TENANT |
| | SPACE COMMON AREAS SHALL NOT FEED INTO TENANT |
| | SPACE(S). |
| | PLEASE CONFIRM THAT THESE OUTLET BOXES ARE ACTUALLY |
| | LOCATED ON THE OUTSIDE OF THIS TENANT SPACE. |
| | |
| | 7) NOTE: PLEASE INDICATE THE REQUIRED SHOW WINDOW |
| | RECEPTACLES PER 210.62 AND LOADS PER 220.43A |
| | |
| | 8) NOTE: RISER SHOWS A 200AMP SERVICE HOWEVER |
| | CONDUCTORS ON RISER ARE ONLY RATED FOR 150AMPS. 310.16 |
| | |
| | 9) NOTE: RISER INDICATES EQUIPMENT GROUNDING CONDUCTOR |
| | BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT |
| | PERMITTED 250.6,250.24 |
| | |
| | 10) NOTE: PLEASE EXPLAIN HOW WATER HEATER IS BEING |
| | FIGURED INTO THE LOAD CALCULATIONS. PLEASE SEE 422.13 |
| | AS WATER HEATER (STORAGE TYPE) ARE CONSIDERED A |
| | CONTINUOUS LOAD AND NEEDS TO BE FIGURED AT 125%. |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |