| Plan Review Notes For Permit 08070687 |
| Permit Number |
08070687 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-07-23 16:39:42 | 2004 FBC W/2007 REVISIONS | | | REROOF FLAT DECK | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS AS | | | REQUIRED BY RULE 9B-72 AND FBC 106.1* CITY AMENDMENTS. | | | | | | 2) SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES, | | | FASTENING OPTION AND DESIGN PRESSURE LISTED IN THE NOA | | | WILL BE USED. FBC R301.1 | | | | | | 3) SUBMIT TWO COPIES OF SIGNED, SEALED AND DATED RAS | | | 117 CALCULATIONS FOR ENHANCED FASTENING AT PERIMETER | | | AND CORNER AREAS FROM AN ENGINEER, ARCHITECT OR | | | REGISTERED ROOF CONSULTANT AS REQUIRED BY LIMITATION | | | NUMBER 7 ON PAGE 26 OF NOA NO. 07-0228.06. NOTE: THE | | | ASSEMBLIES WITH LIMITATION #9 CAN NOT BE USED BECAUSE | | | THE DESIGN PRESSURES ARE TOO LOW AND THEY CAN NOT BE | | | INCREASED. THE STRUCTURE IS LOCATED IN EXPOSURE | | | CATEGORY C. | | | | | | 4) PROVIDE DOCUMENTATION THAT THE GENERAL CONTRACTOR'S | | | LICENSE # CGCB03083 LISTED ON THE APPLICATION ALLOWS | | | THE CONTRACTOR TO PERFORM REROOFING WORK WITHOUT A | | | ROOFING CONTRACTING LICENSE AS REQUIRED BY FS 489.113. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|