Plan Review Notes
Plan Review Notes For Permit 08070649
Permit Number 08070649
Review Stop E
Sequence Number 1
Notes
Date Text
2008-07-29 12:09:46 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC CHAPTER 1 AS AMENDED AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 250.52(A)(3) CONCRETE-ENCASED ELECTRODE AN ELECTRODE
 ENCASED BY AT LEAST 50 MM (2 IN.) OF CONCRETE, LOCATED
 WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR
 FOOTING THAT IS IN DIRECT CONTACT WITH THE EARTH,
 CONSISTING OF AT LEAST 6.0 M (20 FT) OF ONE OR MORE
 BARE OR ZINC GALVANIZED OR OTHER ELECTRICALLY
 CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT
 LESS THAN 13 MM ( 1/ 2 IN.) IN DIAMETER, OR CONSISTING
 OF AT LEAST 6.0 M (20 FT) OF BARE COPPER CONDUCTOR NOT
 SMALLER THAN 4 AWG. REINFORCING BARS SHALL BE PERMITTED
 TO BE BONDED TOGETHER BY THE USUAL STEEL TIE WIRES OR
 OTHER EFFECTIVE MEANS.**INDICATE COMPLIANCE ON THE
 PLAN.
  
 2} } PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 INCLUDING THE METER ENCLOSURE, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED.SEE 230.70(A)(1)
 REGARDING LOCATION WITH RELATION TO THE FIRST MEANS OF
 DISCONNECT.
  
 3} THE METER SHOWN ON THE RISER IS SHOWN AS 150 AMP,
 THE PANEL IS SHOWN AS A 200 AMP MCP.THE #1 SERVICE
 CONDUCTORS ARE RATED FOR 150 AMPS PER 310.15(B)(6), AND
 ARE IN VIOLATION OF OF THAT ARTICLE AND 240.6 BY
 TERMINATING IN 200AMP OCP.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 5} 210.70(A)(2)(B) FOR DWELLING UNITS, ATTACHED
 GARAGES, AND DETACHED GARAGES WITH ELECTRIC POWER, AT
 LEAST ONE WALL SWITCH?CONTROLLED LIGHTING OUTLET SHALL
 BE INSTALLED TO PROVIDE ILLUMINATION ON THE EXTERIOR
 SIDE OF OUTDOOR ENTRANCES OR EXITS WITH GRADE LEVEL
 ACCESS. A VEHICLE DOOR IN A GARAGE SHALL NOT BE
 CONSIDERED AS AN OUTDOOR ENTRANCE OR EXIT. ***LOCATE
 SAME ON PLANS.
  
 NOTE: THE 2007 REVISIONS TO THE 2004 FBC HAS BEEN
 ADOPTED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718