Plan Review Notes
Plan Review Notes For Permit 08070649
Permit Number 08070649
Review Stop B
Sequence Number 1
Notes
Date Text
2008-08-05 16:56:36RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT
 PICK UP.
  
 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH
 COUNTY 2300 N JOG RD (561)233-5120 TO VERIFY IF IMPACT
 FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF
 IMPACT FEES PAID RECEIPT IF FEES ARE DUE.
  
 3-A) ACCORDING TO SEC. R301.2.1.4(3) OF 2004 FLORIDA
 RESIDENTIAL CODE THE BUILDINGIS LOCATED IN EXPOSURE
 CATEGORY "C". REVISE DESIGN INFORMATION ON SHEET 1 OF
 10 AND 10 OF 10 AS REQUIRED.
  
 B)CLARIFY HOW IS THE BUILDING DESIGNED AS ENCLOSED
 IF SOFFIT ON STUDIO AREA IS OPEN AND IF COVERED PORCH
 IS OPEN ON THREESIDES.SEC. 106.1.2 CITY AMENDMENTS
 TO FBC 2004TO VERIFY COMPLIANCE WITH DESIGN LOADS OF
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
  
 4- PROVIDE SOIL TEST REPORT.SEC. R401.4 OF 2004
 FLORIDA RESIDENTIAL CODE.
  
 5- SPECIFYOPENINGS DESIGN PRESSURES AS REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE.
 NOTE:COORDINATE WITH ITEM #3 ABOVE.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR:
 A) FRENCH DOORS AS SHOWN ON PLANS.PROVIDE COMPLETE
 PRODUCT APPROVAL REPORT.FLORIDA PRODUCT APPROVAL
 FL7133 SUBMITTED IS MISSING THE TECHNICAL DRAWINGS
 SHOWING THE APPROVED DOORS.
  
 B) STORM SHUTTERS IF DOORS AND WINDOWS DON'T HAVE
 IMPACT GLAZING.
 ALSO, PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE
 ATTACHED SAMPLE.
  
 C) SINGLE HUNG WINDOWS. PROVIDE COMPLETE PRODUCT
 APPROVAL REPORT. PRODUCT APPROVAL FL239-R11
 SUBMITTED IS MISSING THE WINDOW DRAWINGS.
  
 D) HORIZONTAL SLIDER WINDOWS. PROVIDE COMPLETE
 PRODUCT APPROVAL REPORT.PRODUCT APPROVAL FL242-R7
 SUBMITTED IS MISSING THE WINDOW DRAWINGS.
  
 E) ROOF SHINGLES.
  
 F) PRECAST LINTELSSPECIFIED ON PLANS AND DETAILS.
  
 G) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
 NOTE:PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED
 TO SUBMITCOMPLETE REPORT.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 8- OWES $16.72 FOR RADON FEES.
  
 9- SURVEY SUBMITTED HAS INCORRECT FLOOD ZONE AND PANEL
 NUMBER.CORRECT INFORMATION IS FLOOD ZONE "B" AND
 CORRECT MAP IS 120192 - 0125 BDATED 10/15/82.
 REVISE AS REQUIRED.
  
 10- SHEET 1 OF 10:SQUARE FOOTAGE DATA DOESN'TADD
 UP. 960 PLUS 711 IS EQUAL TO 1671, NOT 1673. REVISE AS
 REQUIRED.
  
 11- SHEET 2 OF 10:IF WINDOWSLOCATED NEXT TO FRENCH
 DOORS ON EASTWALL OF STUDIO DON'T HAVE IMPACT GLASS,
 THEN THEY NEEDHAVE SAFETY GLAZING AS REQUIRED BY SEC.
 R308.4(6) OF 2004 FLORIDA RESIDENTIAL CODE.SPECIFY ON
 PLANS AS REQUIRED.
  
 12- SHEET 6 OF 10:A) SPECIFY SPACING FOR 2X 10
 RAFTERS ON COVERED PATIO AREA.
  
 B) SPECIFY ROOF PITCH.
  
 C) SPECIFY CALCULATED UPLIFT LOADS AS REQUIRED BY
 SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE TO VERIFY
 COMPLIANCE WITH SPECIFIED CONNECTOR (ONE H1 SIMPSON
 CONNECTION BETWEEN RAFTER AND (3)2X12 BEAM IN OPEN
 COVERED PATIO AREA.AND ONLY ONE H1 SIMPSON CONNECTOR
 BETWEEN RAFTER AND DOUBLE 2X PLATE ON ENCLOSED STUDIO
 AREA.)
  
 D) PROVIDE COMPLETE FRAMING DETAIL AT GABLE ENDS
 SHOWING COMPLIANCE WITH SEC. R601.2 OF 2004 FLORIDA
 RESIDENTIAL CODE.HOW ARE THE LOADS TRANSFERRED TO THE
 GABLE END WALL?.
  
 13-SHEET 8 OF 10:CLARIFY/REVISE SIZE OF T & G ROOF
 SHEATHING.DETAIL ON COVERED PATIO SECTION SAYS 5/4" T
 & G SHEATHING, WHILE DETAIL ON COVERED PATIO WALL
 SECTION SAYS 3/4" X 6" T & G SHEATHING.
  
 14- SHEET 9OF 10:REVISE LINTEL SCHEDULE TO MATCH
 PLANS.MISSING L-3 AND SIZE OF L-2 IS INCORRECT.
  
 15- SHEET 10 OF 10:
 A) UPDATE GENERAL STRUCTURAL NOTE # 4(A). SPECIFY
 CURRENT CODE. VERSION.
  
 B) UPDATE YEAR REFERENCE FOR MASONRY NOTE#1. SEE
 CHAPTER43 OF 2004 FLORIDA RESIDENTIAL CODE FOR
 CURRENT YEAR TO BE USED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712