| 2008-08-05 16:56:36 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY |
| | SEC. 713.13 FLORIDA STATUTE. |
| | NOTE: THIS MAY BE PROVIDED LATER AT TIME OF PERMIT |
| | PICK UP. |
| | |
| | 2- AFTER PLANS ARE REVISED BRING THEM TO PALM BEACH |
| | COUNTY 2300 N JOG RD (561)233-5120 TO VERIFY IF IMPACT |
| | FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF |
| | IMPACT FEES PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3-A) ACCORDING TO SEC. R301.2.1.4(3) OF 2004 FLORIDA |
| | RESIDENTIAL CODE THE BUILDINGIS LOCATED IN EXPOSURE |
| | CATEGORY "C". REVISE DESIGN INFORMATION ON SHEET 1 OF |
| | 10 AND 10 OF 10 AS REQUIRED. |
| | |
| | B)CLARIFY HOW IS THE BUILDING DESIGNED AS ENCLOSED |
| | IF SOFFIT ON STUDIO AREA IS OPEN AND IF COVERED PORCH |
| | IS OPEN ON THREESIDES.SEC. 106.1.2 CITY AMENDMENTS |
| | TO FBC 2004TO VERIFY COMPLIANCE WITH DESIGN LOADS OF |
| | SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 4- PROVIDE SOIL TEST REPORT.SEC. R401.4 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- SPECIFYOPENINGS DESIGN PRESSURES AS REQUIRED BY |
| | SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | NOTE:COORDINATE WITH ITEM #3 ABOVE. |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) FRENCH DOORS AS SHOWN ON PLANS.PROVIDE COMPLETE |
| | PRODUCT APPROVAL REPORT.FLORIDA PRODUCT APPROVAL |
| | FL7133 SUBMITTED IS MISSING THE TECHNICAL DRAWINGS |
| | SHOWING THE APPROVED DOORS. |
| | |
| | B) STORM SHUTTERS IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLAZING. |
| | ALSO, PROVIDE COMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE. |
| | |
| | C) SINGLE HUNG WINDOWS. PROVIDE COMPLETE PRODUCT |
| | APPROVAL REPORT. PRODUCT APPROVAL FL239-R11 |
| | SUBMITTED IS MISSING THE WINDOW DRAWINGS. |
| | |
| | D) HORIZONTAL SLIDER WINDOWS. PROVIDE COMPLETE |
| | PRODUCT APPROVAL REPORT.PRODUCT APPROVAL FL242-R7 |
| | SUBMITTED IS MISSING THE WINDOW DRAWINGS. |
| | |
| | E) ROOF SHINGLES. |
| | |
| | F) PRECAST LINTELSSPECIFIED ON PLANS AND DETAILS. |
| | |
| | G) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. |
| | NOTE:PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE WHERE CONNECTOR IS SHOWN. NO NEED |
| | TO SUBMITCOMPLETE REPORT. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING)ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 8- OWES $16.72 FOR RADON FEES. |
| | |
| | 9- SURVEY SUBMITTED HAS INCORRECT FLOOD ZONE AND PANEL |
| | NUMBER.CORRECT INFORMATION IS FLOOD ZONE "B" AND |
| | CORRECT MAP IS 120192 - 0125 BDATED 10/15/82. |
| | REVISE AS REQUIRED. |
| | |
| | 10- SHEET 1 OF 10:SQUARE FOOTAGE DATA DOESN'TADD |
| | UP. 960 PLUS 711 IS EQUAL TO 1671, NOT 1673. REVISE AS |
| | REQUIRED. |
| | |
| | 11- SHEET 2 OF 10:IF WINDOWSLOCATED NEXT TO FRENCH |
| | DOORS ON EASTWALL OF STUDIO DON'T HAVE IMPACT GLASS, |
| | THEN THEY NEEDHAVE SAFETY GLAZING AS REQUIRED BY SEC. |
| | R308.4(6) OF 2004 FLORIDA RESIDENTIAL CODE.SPECIFY ON |
| | PLANS AS REQUIRED. |
| | |
| | 12- SHEET 6 OF 10:A) SPECIFY SPACING FOR 2X 10 |
| | RAFTERS ON COVERED PATIO AREA. |
| | |
| | B) SPECIFY ROOF PITCH. |
| | |
| | C) SPECIFY CALCULATED UPLIFT LOADS AS REQUIRED BY |
| | SEC. R301 OF 2004 FLORIDA RESIDENTIAL CODE TO VERIFY |
| | COMPLIANCE WITH SPECIFIED CONNECTOR (ONE H1 SIMPSON |
| | CONNECTION BETWEEN RAFTER AND (3)2X12 BEAM IN OPEN |
| | COVERED PATIO AREA.AND ONLY ONE H1 SIMPSON CONNECTOR |
| | BETWEEN RAFTER AND DOUBLE 2X PLATE ON ENCLOSED STUDIO |
| | AREA.) |
| | |
| | D) PROVIDE COMPLETE FRAMING DETAIL AT GABLE ENDS |
| | SHOWING COMPLIANCE WITH SEC. R601.2 OF 2004 FLORIDA |
| | RESIDENTIAL CODE.HOW ARE THE LOADS TRANSFERRED TO THE |
| | GABLE END WALL?. |
| | |
| | 13-SHEET 8 OF 10:CLARIFY/REVISE SIZE OF T & G ROOF |
| | SHEATHING.DETAIL ON COVERED PATIO SECTION SAYS 5/4" T |
| | & G SHEATHING, WHILE DETAIL ON COVERED PATIO WALL |
| | SECTION SAYS 3/4" X 6" T & G SHEATHING. |
| | |
| | 14- SHEET 9OF 10:REVISE LINTEL SCHEDULE TO MATCH |
| | PLANS.MISSING L-3 AND SIZE OF L-2 IS INCORRECT. |
| | |
| | 15- SHEET 10 OF 10: |
| | A) UPDATE GENERAL STRUCTURAL NOTE # 4(A). SPECIFY |
| | CURRENT CODE. VERSION. |
| | |
| | B) UPDATE YEAR REFERENCE FOR MASONRY NOTE#1. SEE |
| | CHAPTER43 OF 2004 FLORIDA RESIDENTIAL CODE FOR |
| | CURRENT YEAR TO BE USED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |