Plan Review Notes
Plan Review Notes For Permit 08070648
Permit Number 08070648
Review Stop B
Sequence Number 5
Notes
Date Text
2008-11-12 11:39:28***CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. IT APPEARS THAT ANCHOR SPACING INTO CONCRETE WAS
 USED, PAGE 10. HOWEVER, "CONCRETE FILLED BLOCK"
 REQUIRES USE OF THE "MASONRY" COLUMN AS THIS DOES NOT
 HAVE THE SAME STRENGTH AS FORMED AND POURED CONCRETE.
 PLEASE REVISE ANCHOR SCHEDULE ACCORDINGLY. EXAMPLES
 WERE PROVIDED IN PREVIOUS REVIEWS.
  
 FOR EXAMPLE, OPENING 4, 1 (TOP) WOULD NOT BE ALLOWED
 (DIFFERENT CONNECTION DETAIL REQUIRED). 9 (BOTTOM)
 WOULD REQUIRE 7" SPACING, NOT 12" AS SPECIFIED.
  
  