| Plan Review Notes For Permit 08070648 |
| Permit Number |
08070648 |
|
| Review Stop |
B |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2008-11-12 11:39:28 | ***CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. IT APPEARS THAT ANCHOR SPACING INTO CONCRETE WAS | | | USED, PAGE 10. HOWEVER, "CONCRETE FILLED BLOCK" | | | REQUIRES USE OF THE "MASONRY" COLUMN AS THIS DOES NOT | | | HAVE THE SAME STRENGTH AS FORMED AND POURED CONCRETE. | | | PLEASE REVISE ANCHOR SCHEDULE ACCORDINGLY. EXAMPLES | | | WERE PROVIDED IN PREVIOUS REVIEWS. | | | | | | FOR EXAMPLE, OPENING 4, 1 (TOP) WOULD NOT BE ALLOWED | | | (DIFFERENT CONNECTION DETAIL REQUIRED). 9 (BOTTOM) | | | WOULD REQUIRE 7" SPACING, NOT 12" AS SPECIFIED. | | | | | | |
|