| Plan Review Notes For Permit 08070648 |
| Permit Number |
08070648 |
|
| Review Stop |
B |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-10-17 15:35:24 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. THIS BUILDING IS LOCATED IN EXPOSURE C, SEE FBC | | | R301.2.1.4. | | | | | | 2. ALTHOUGH DESIGN PRESSURES ARE GREATER THAN -40PSF, | | | IT APPEARS THAT THE CHART FOR -40PSF HAS BEEN USED TO | | | SPECIFY ANCHOR SPACING. PLEASE SEE CHARTS ON SHEET 10 | | | (NOT SHEET 9). FOR INSTANCE, SEE OPENING 4. FOR A | | | PRESSURE OF -40.08, CONNECTION TYPE 2, TOP, INTO | | | BLOCKIS NOT ALLOWED. CONNECTION TYPE 11 BOTTOM REQUIRES | | | 4 1/2" ANCHOR SPACING; 11" SPECIFIED. PLEASE REVISE. | | | | | | |
|