| 2008-10-02 10:21:32 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2004 |
| | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | |
| | 1. +-40PSF HAS BEEN HIGHLIGHTED ON THE PRODUCT |
| | APPROVALS (FOR INSTANCE, SEE SHEET 9 OF THE STORM PANEL |
| | PA). HOWEVER, THE INSTALLATION SCHEDULE STATES THAT |
| | DESIGN PRESSURE IS +-60PSF FOR SOME OPENINGS; +-90PSF |
| | FOR OTHERS. THE DISCREPANCY IN DESIGN PRESSURE HAS |
| | RESULTED IN OTHER COMMENTS. INFORMATION HIGHLIGHTED ON |
| | THE PRODUCT APPROVALS SHOULD BE CONSISTENT WITH THE |
| | INSTALLATION SCHEDULE AND THE JOB. FBC R 301. |
| | |
| | 2. SEE OPENING 4 AND SHEET 10 OF THE STORM PANEL |
| | PRODUCT APPROVAL; SHUTTER CONNECTION MOUNTING TYPE 2 |
| | TOP, TAPCON, MASONRY (BLOCK), 60 PSF CANNOT BE USED. |
| | THIS APPLIES TO OTHER OPENINGS. |
| | |
| | 3. SEE OPENING 4 AND SHEET 10 OF THE STORM PANEL PA; |
| | MOUNTING TYPE 11 BOTTOM, BLOCK, -60PSF REQUIRES 4" |
| | ANCHOR SPACING. |
| | |
| | 4. SHEET 10, ACCORDION PRODUCT APPROVAL, WALL MOUNT 3 |
| | IS HIGHLIGHTED BUT INSTALLATION SCHEDULE SPECIFIES "C", |
| | OPENING 7. WHAT IS C? THIS SHOULD CORRELATE WITH THE |
| | ANCHOR CHARTS. |
| | |
| | 5. OPENING 7, WALL MOUNT 3 (HIGHLIGHTED ON THE PRODUCT |
| | APPROVAL), -90PSF REQUIRES 4" ANCHOR SPACING, SEE SHEET |
| | 10. |
| | |
| | 6. ALL COMMENTS APPLY TO OTHER OPENINGS; THESE SPECIFIC |
| | OPENINGS WERE PROVIDED AS AN EXAMPLE. |
| | |