Notes
Date Text
2008-10-02 10:21:32****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
  
 1. +-40PSF HAS BEEN HIGHLIGHTED ON THE PRODUCT
 APPROVALS (FOR INSTANCE, SEE SHEET 9 OF THE STORM PANEL
 PA). HOWEVER, THE INSTALLATION SCHEDULE STATES THAT
 DESIGN PRESSURE IS +-60PSF FOR SOME OPENINGS; +-90PSF
 FOR OTHERS. THE DISCREPANCY IN DESIGN PRESSURE HAS
 RESULTED IN OTHER COMMENTS. INFORMATION HIGHLIGHTED ON
 THE PRODUCT APPROVALS SHOULD BE CONSISTENT WITH THE
 INSTALLATION SCHEDULE AND THE JOB. FBC R 301.
  
 2. SEE OPENING 4 AND SHEET 10 OF THE STORM PANEL
 PRODUCT APPROVAL; SHUTTER CONNECTION MOUNTING TYPE 2
 TOP, TAPCON, MASONRY (BLOCK), 60 PSF CANNOT BE USED.
 THIS APPLIES TO OTHER OPENINGS.
  
 3. SEE OPENING 4 AND SHEET 10 OF THE STORM PANEL PA;
 MOUNTING TYPE 11 BOTTOM, BLOCK, -60PSF REQUIRES 4"
 ANCHOR SPACING.
  
 4. SHEET 10, ACCORDION PRODUCT APPROVAL, WALL MOUNT 3
 IS HIGHLIGHTED BUT INSTALLATION SCHEDULE SPECIFIES "C",
 OPENING 7. WHAT IS C? THIS SHOULD CORRELATE WITH THE
 ANCHOR CHARTS.
  
 5. OPENING 7, WALL MOUNT 3 (HIGHLIGHTED ON THE PRODUCT
 APPROVAL), -90PSF REQUIRES 4" ANCHOR SPACING, SEE SHEET
 10.
  
 6. ALL COMMENTS APPLY TO OTHER OPENINGS; THESE SPECIFIC
 OPENINGS WERE PROVIDED AS AN EXAMPLE.
  