| Plan Review Notes For Permit 08070648 |
| Permit Number |
08070648 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-08-29 10:46:32 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBC FLORIDA BUILDING CODE 2004 | | | FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FS FLORIDA STATUTE | | | | | | 1. SEE ALL OPENINGS. NA WAS WRITTEN IN THE COLUMN FOR | | | SHUTTER CONNECTION MOUNTING TYPE. THIS SHOULD CORRELATE | | | WITH THE ANCHOR CHARTS; FOR INSTANCE, ACCORDION, PAGE | | | 10, MOUNTING TYPE WOULD BE A THROUGH L FOR ACCORDIONS, | | | AND (AN EXAMPLE) 1 TOP, 1 BOTTOM FOR STORM PANELS (SEE | | | SHEET 9). | | | | | | 2. MOUNTING TYPE A WAS HIGHLIGHTED ON THE ACCORDION | | | SHUTTER PRODUCT APPROVAL; THIS REQUIRES A CONCRETE | | | SUBSTRATE, NOT BLOCK. | | | | | | 3. A 2" EDGE DISTANCE REQUIRES A .50 FACTOR, SEE PAGE | | | 11 OF ACCORDION PRODUCT APPROVAL, PAGE 9 OF PANEL | | | PRODUCT APPROVAL. | | | | | | 4. SEE OPENINGS 4, 5, 6. YOU'VE HIGHLIGHTED THE COLUMN | | | FOR CONCRETE ON THE PRODUCT APPROVAL, 12" ANCHOR | | | SPACING, BUT INSTALLATION SCHEDULE STATES THIS IS | | | BLOCK. YOU MUST USE THE MASONRY COLUMN FOR BLOCK. | | | | | | |
|