| Plan Review Notes For Permit 08070647 |
| Permit Number |
08070647 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-08-05 15:25:22 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.SEE PAGE 14, A 2 1/2 INCH EDGE DISTANCE REQUIRES A | | | FACTOR OF .66 APPLIED TO THE ANCHOR SPACING. | | | | | | 2.PLEASE REVISE THE SHUTTER CONNECTION MOUNTING TYPE | | | TO CORRELATE WITH THE ANCHOR CHART; A THROUGH L. | | | | | | 3. CLARIFY SUBSTRATE. |
|