| Notes |
| Date |
Text |
| 2009-03-09 15:47:09 | ****PROVISO**** | | | PAGES M-1 THROUGH M-4: NOTE #1 CALLS FOR 1" COPPER PIPE | | | TO BE TRANSITIONED TO 3/4 PVC PIPE. CONDENSATE PIPE | | | SHALL NOT DECREASE IN SIZE FROM THE DRAIN PAN | | | CONNECTION TO THE PLACE OF CONDENSATE DISPOSAL IN | | | ACCORDANCE WITH FBC-M 307.2.2. IF PIPE STARTS AS 1" IT | | | MUST STAY AT 1". PIPE MAY ALSO START AT 3/4" AS LONG AS | | | IT DOES NOT REDUCE IN SIZE. REVISE PLANS PRIOR TO | | | INSPECTION TO ADDRESS THIS CONDITION IN ACCORDANCE WITH | | | FBC-B 106.4. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|