| | ** PROVISO ITEMS ** |
| | |
| | THE FOLLOWING CORRECTIONS WILL BE NEEDED ALONG WITH ANY |
| | OTHER REVISIONS BEFORE ROUGH ELECTRICAL INSPECTIONS. |
| | |
| | 1) NOTE: LOAD CALCULATIONS NEED TO BE REVISED. THE ONE |
| | OR MORE SMALL APPLIANCE CIRCUITS SHALL BE 1500VA FOR |
| | EACH. AS THERE ARE THREE PER 210.52B1, 210.11C1 EACH |
| | SHALL BE THE 1500VA PER 220.52. |
| | ONLY TWO ARE SHOWN FOR A TOTAL OF 3000VA. THE DEDICATED |
| | DINING ROOM CIRCUIT IS NOT FIGURED INTO CALCULATIONS. |
| | THIS WOULD BE A TOTAL OF 4500VA. |
| | |
| | 2) NOTE: THE PANEL SCHEDULE FOR THE HOUSE LOADS STILL |
| | SHOW THE DEDICATED CIRCUITS FOR THE OUTSIDE LIGHTING OF |
| | EACH BUILDING. HOWEVER THE LIGHTING ON THE OUTSIDE OF |
| | EACH UNIT IS NOT FED FROM THE HOUSE PANEL. EACH FIXTURE |
| | IS ON EACH OF THE UNITS. |
| | PLEASE REVISE THE PANELS AND LOADS. 408.4, 220 |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| 2009-03-06 16:36:35 | ELECTRICAL REVIEW WILL BE A PROVISO HOWEVER ON HOLD FOR |
| | ADDRESSING CORRECTIONS TO BE MADE. |
| | |
| | ** TEMPORARY FAILED STATUS FOR THE ADDRESSING TO BE |
| | REVIEWED. |
| | BOTH BUILDINGS ARE APPLIED UNDER ONE PERMIT AND ONE |
| | ADDRESS ALTHOUGH EACH BUILDING IS COMPLETELY SEPARATE. |
| | THE ADDRESSING REVIEWER HAS ADDED ADDRESSES FOR EACH |
| | UNIT AS A SEPARATE OWN LOCATION. THIS NEEDS TO BE GONE |
| | OVER BEFORE ISSUANCE. |
| | EACH BUILDING SHALL CONTAIN ITS OWN ADDRESS. HOWEVER |
| | THERE IS ONLY ONE PERMIT APPLICATION AT THIS TIME FOR |
| | BOTH BUILDINGS. THE CONTRACTOR NEEDS TO BE AWARE THAT |
| | BOTH BUILDINGS MUST BE COMPLETE BEFORE C OF O CAN BE |
| | GRANTED FOR EITHER OF THE BUILDINGS. |
| | ALSO THESE ARE NOT FEE SIMPLE UNITS. THE ADDRESSING IS |
| | BASED ON THE BUILDING WITH EACH UNIT BEING A |
| | SUITE/UNIT/OR APARTMENT NUMBER. EACH BUILDING HAS ONLY |
| | ONE ELECTRICAL SERVICE AS THIS IS A MULTI-FAMILY |
| | BUILDING. |
| | THE REVIEW WILL REMAIN IN A FAILED STATUS UNTIL |
| | APPLICATION/ADDRESSING IS CLEARED UP. THE INFORMATION |
| | WAS ROUTED TO THE ADDRESSING REVIEWER AND WILL BE GONE |
| | OVER. |
| | |
| | REVIEW WILL GO INTO A PASSED STATUS WITH PROVISO AFTER |
| | ADDRESSING IS CORRECTED. |
| | |
| | |
| | |
| | |
| | |