 ** PROVISO ITEMS **
  
 THE FOLLOWING CORRECTIONS WILL BE NEEDED ALONG WITH ANY
 OTHER REVISIONS BEFORE ROUGH ELECTRICAL INSPECTIONS.
  
 1) NOTE: LOAD CALCULATIONS NEED TO BE REVISED. THE ONE
 OR MORE SMALL APPLIANCE CIRCUITS SHALL BE 1500VA FOR
 EACH. AS THERE ARE THREE PER 210.52B1, 210.11C1 EACH
 SHALL BE THE 1500VA PER 220.52.
 ONLY TWO ARE SHOWN FOR A TOTAL OF 3000VA. THE DEDICATED
 DINING ROOM CIRCUIT IS NOT FIGURED INTO CALCULATIONS.
 THIS WOULD BE A TOTAL OF 4500VA.
  
 2) NOTE: THE PANEL SCHEDULE FOR THE HOUSE LOADS STILL
 SHOW THE DEDICATED CIRCUITS FOR THE OUTSIDE LIGHTING OF
 EACH BUILDING. HOWEVER THE LIGHTING ON THE OUTSIDE OF
 EACH UNIT IS NOT FED FROM THE HOUSE PANEL. EACH FIXTURE
 IS ON EACH OF THE UNITS.
 PLEASE REVISE THE PANELS AND LOADS. 408.4, 220
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
2009-03-06 16:36:35ELECTRICAL REVIEW WILL BE A PROVISO HOWEVER ON HOLD FOR
 ADDRESSING CORRECTIONS TO BE MADE.
  
 ** TEMPORARY FAILED STATUS FOR THE ADDRESSING TO BE
 REVIEWED.
 BOTH BUILDINGS ARE APPLIED UNDER ONE PERMIT AND ONE
 ADDRESS ALTHOUGH EACH BUILDING IS COMPLETELY SEPARATE.
 THE ADDRESSING REVIEWER HAS ADDED ADDRESSES FOR EACH
 UNIT AS A SEPARATE OWN LOCATION. THIS NEEDS TO BE GONE
 OVER BEFORE ISSUANCE.
 EACH BUILDING SHALL CONTAIN ITS OWN ADDRESS. HOWEVER
 THERE IS ONLY ONE PERMIT APPLICATION AT THIS TIME FOR
 BOTH BUILDINGS. THE CONTRACTOR NEEDS TO BE AWARE THAT
 BOTH BUILDINGS MUST BE COMPLETE BEFORE C OF O CAN BE
 GRANTED FOR EITHER OF THE BUILDINGS.
 ALSO THESE ARE NOT FEE SIMPLE UNITS. THE ADDRESSING IS
 BASED ON THE BUILDING WITH EACH UNIT BEING A
 SUITE/UNIT/OR APARTMENT NUMBER. EACH BUILDING HAS ONLY
 ONE ELECTRICAL SERVICE AS THIS IS A MULTI-FAMILY
 BUILDING.
 THE REVIEW WILL REMAIN IN A FAILED STATUS UNTIL
 APPLICATION/ADDRESSING IS CLEARED UP. THE INFORMATION
 WAS ROUTED TO THE ADDRESSING REVIEWER AND WILL BE GONE
 OVER.
  
 REVIEW WILL GO INTO A PASSED STATUS WITH PROVISO AFTER
 ADDRESSING IS CORRECTED.
  
  
  
  
  