| 2008-08-05 09:47:41 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | |
| | 1. SHT P-1 SHOWS VENTS AT THE CURB OF THE SHOWER IN |
| | UNITS "A". PLEASE CLARIFY. WILL THIS BE A SOLID WALL |
| | WITH A DOOR? 106.1.2. |
| | |
| | 2. SHT P-2 TUBS INDICATED AS SHOWERS IN THE MASTER |
| | BATHROOMS OF "A" & "B" UNITS ARE NOT VENTED. SECTION |
| | 901.2.1. |
| | |
| | 3. SHT P-3 THE WASH MACHINES IN THE "B" UNITS AND ONE |
| | "C" UNIT SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL |
| | WET VENT FOR THE BATHROOM FIXTURES. SECTION 909.1. |
| | |
| | 4. SHT P-3 THE FLOOR PLANS FOR THE WASH MACHINES AND |
| | WATER HEATERS ARE DIFFERENT IN BOTH "C" UNITS. AS SUCH |
| | SEPARATE RISER DIAGRAMS REFLECTING THE DIFFERENT FLOOR |
| | PLANS WILL BE REQUIRED FOR THE SANITARY AND WATER |
| | ISOMETRICS. SECTION 106.3.5.1.3. |
| | |
| | 5. SHT P-4 TUBS INDICATED AS SHOWERS IN THE MASTER |
| | BATHROOMS OF THE "B" UNITS ARE NOT VENTED. SECTION |
| | 901.2.1. |
| | |
| | 6. SHT P-5 SANITARY RISER DIAGRAM UNIT "A"DOES NOT |
| | REFLECT THE FLOOR PLAN FIRST FLOOR. THE VENT AT THE |
| | SHOWER IS NOT SHOWN AND AS SUCH IS NOT VENTED. THE |
| | "SHOWER" FOR THE MASTER BATH IS NOT VENTED. (THIS IS |
| | SHOWN AS A TUB ON THE FLOOR PLAN). SECTIONS 106.1.1 & |
| | 901.2.1. |
| | |
| | 7. SHT P-5 SANITARY RISER DIAGRAM UNIT "B"DOES NOT |
| | REFLECT THE FLOOR PLAN FIRST FLOOR. THE WASH MACHINE IS |
| | SHOWN CONNECTING DOWNSTREAM OF THE WATER CLOSET ON THE |
| | FLOOR PLAN, BUT BETWEEN THE WATER CLOSET AND LAV ON THE |
| | RISER DIAGRAM. (SEE SECTION 909.1). THE MASTER BATH |
| | SHOWER, (SHOWN AS A TUB ON THE FLOOR PLAN), IS NOT |
| | VENTED. SECTIONS 106.1.1 & 901.2.1. |
| | |
| | 8. SHT P-5 SANITARY RISER DIAGRAM UNIT "C" DOES NOT |
| | REFLECT THE FLOOR PLAN FIRST FLOOR. THE STACK FOR THE |
| | SECOND FLOOR BATHROOM IS SHOWN CONNECTING TO THE BRANCH |
| | LINE TO THE POWDER ROOM ON THE FLOOR PLAN, BUT ON THE |
| | BRANCH LINE TO THE WASH MACHINE ON THE RISER DIAGRAM. |
| | ALSO THE WASH MACHINE IS SHOWN UPSTREAM OF THE KITCHEN |
| | SINK ON THE FLOOR PLAN BUT DOWNSTREAM OF THE KITCHEN |
| | SINK ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTIONS |
| | 106.1.1 & 710.1. |
| | |
| | 9. SHT P-6 WATER RISER DIAGRAM UNIT "A" DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE WATER HEATER. FLOOR PLAN |
| | SHOWS THE WATER HEATER BETWEEN THE BATHROOM FIXTURES |
| | AND THE WASH MACHINE BUT THE RISER DIAGRAM SHOWS THE |
| | WATER HEATER PAST THE KITCHEN SINK BRANCH LINE. PLEASE |
| | CORRELATE. SECTIONS 106.1.1 & 604.1. |
| | |
| | 10. SHT P-6 WATER RISER DIAGRAM UNIT "C" DOES NOT |
| | REFLECT THE FLOOR PLAN AT THE WATER HEATER. FLOOR PLAN |
| | SHOWS THE WATER HEATER BETWEEN THE BATHROOM FIXTURES |
| | AND THE WASH MACHINE BUT THE RISER DIAGRAM SHOWS THE |
| | WATER HEATER PAST THE KITCHEN SINK AND THE WASH MACHINE |
| | BRANCH LINES. PLEASE CORRELATE. SECTIONS 106.1.1 & |
| | 604.1. |
| | |
| | 11. SHT P-6 ALL WATER RISER DIAGRAMS. WATER HAMMER |
| | ARRESTORS ARE REQUIRED AT THE WASH MACHINES, DISH |
| | WASHERS & ICE MAKERS (REF) PER SECTION 604.9. THE WATER |
| | HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN |
| | AN "EFFECTIVE RANGE" (NOT IN THE CEILING). PDI-WH 201. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |