 REFERENCE: FBC-2004 PLUMBING
  
 1. SHT P-1 SHOWS VENTS AT THE CURB OF THE SHOWER IN
 UNITS "A". PLEASE CLARIFY. WILL THIS BE A SOLID WALL
 WITH A DOOR? 106.1.2.
  
 2. SHT P-2 TUBS INDICATED AS SHOWERS IN THE MASTER
 BATHROOMS OF "A" & "B" UNITS ARE NOT VENTED. SECTION
 901.2.1.
  
 3. SHT P-3 THE WASH MACHINES IN THE "B" UNITS AND ONE
 "C" UNIT SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT FOR THE BATHROOM FIXTURES. SECTION 909.1.
  
 4. SHT P-3 THE FLOOR PLANS FOR THE WASH MACHINES AND
 WATER HEATERS ARE DIFFERENT IN BOTH "C" UNITS. AS SUCH
 SEPARATE RISER DIAGRAMS REFLECTING THE DIFFERENT FLOOR
 PLANS WILL BE REQUIRED FOR THE SANITARY AND WATER
 ISOMETRICS. SECTION 106.3.5.1.3.
  
 5. SHT P-4 TUBS INDICATED AS SHOWERS IN THE MASTER
 BATHROOMS OF THE "B" UNITS ARE NOT VENTED. SECTION
 901.2.1.
  
 6. SHT P-5 SANITARY RISER DIAGRAM UNIT "A"DOES NOT
 REFLECT THE FLOOR PLAN FIRST FLOOR. THE VENT AT THE
 SHOWER IS NOT SHOWN AND AS SUCH IS NOT VENTED. THE
 "SHOWER" FOR THE MASTER BATH IS NOT VENTED. (THIS IS
 SHOWN AS A TUB ON THE FLOOR PLAN). SECTIONS 106.1.1 &
 901.2.1.
  
 7. SHT P-5 SANITARY RISER DIAGRAM UNIT "B"DOES NOT
 REFLECT THE FLOOR PLAN FIRST FLOOR. THE WASH MACHINE IS
 SHOWN CONNECTING DOWNSTREAM OF THE WATER CLOSET ON THE
 FLOOR PLAN, BUT BETWEEN THE WATER CLOSET AND LAV ON THE
 RISER DIAGRAM. (SEE SECTION 909.1). THE MASTER BATH
 SHOWER, (SHOWN AS A TUB ON THE FLOOR PLAN), IS NOT
 VENTED. SECTIONS 106.1.1 & 901.2.1.
  
 8. SHT P-5 SANITARY RISER DIAGRAM UNIT "C" DOES NOT
 REFLECT THE FLOOR PLAN FIRST FLOOR. THE STACK FOR THE
 SECOND FLOOR BATHROOM IS SHOWN CONNECTING TO THE BRANCH
 LINE TO THE POWDER ROOM ON THE FLOOR PLAN, BUT ON THE
 BRANCH LINE TO THE WASH MACHINE ON THE RISER DIAGRAM.
 ALSO THE WASH MACHINE IS SHOWN UPSTREAM OF THE KITCHEN
 SINK ON THE FLOOR PLAN BUT DOWNSTREAM OF THE KITCHEN
 SINK ON THE RISER DIAGRAM. PLEASE CORRELATE. SECTIONS
 106.1.1 & 710.1.
  
 9. SHT P-6 WATER RISER DIAGRAM UNIT "A" DOES NOT
 REFLECT THE FLOOR PLAN AT THE WATER HEATER. FLOOR PLAN
 SHOWS THE WATER HEATER BETWEEN THE BATHROOM FIXTURES
 AND THE WASH MACHINE BUT THE RISER DIAGRAM SHOWS THE
 WATER HEATER PAST THE KITCHEN SINK BRANCH LINE. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 604.1.
  
 10. SHT P-6 WATER RISER DIAGRAM UNIT "C" DOES NOT
 REFLECT THE FLOOR PLAN AT THE WATER HEATER. FLOOR PLAN
 SHOWS THE WATER HEATER BETWEEN THE BATHROOM FIXTURES
 AND THE WASH MACHINE BUT THE RISER DIAGRAM SHOWS THE
 WATER HEATER PAST THE KITCHEN SINK AND THE WASH MACHINE
 BRANCH LINES. PLEASE CORRELATE. SECTIONS 106.1.1 &
 604.1.
  
 11. SHT P-6 ALL WATER RISER DIAGRAMS. WATER HAMMER
 ARRESTORS ARE REQUIRED AT THE WASH MACHINES, DISH
 WASHERS & ICE MAKERS (REF) PER SECTION 604.9. THE WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR THE FIXTURES IN
 AN "EFFECTIVE RANGE" (NOT IN THE CEILING). PDI-WH 201.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  